CPSM | CCS – Cellar |
Mode | between 50°f - 67°f. |
(Cont.) |
|
| CCT - Cellar |
|
|
| Con/Cof – Compressor On time (Con) and Off time (Cof) with a Probe 1 failure/Alarm. These |
| parameters are set at Con 40 min/Cof 10 min. In the event that there is a Probe 1 failure/Alarm, |
| the compressor/refrigeration system automatically starts a predetermined ON/OFF cycle, which |
| is controlled by the Con and the Cof parameters. The customer can adjust these parameters to |
| maintain the desired Bottle temperature. |
| Hes – Differential for Energy Reduction – This parameter is set at 4° above the set point, dur- |
| ing the Energy Reduction mode. A decrease in this setting will decrease the set point, and an |
| increase in this feature will increase the set point. |
AUX | “AUX” indicates that the evaporator temperature is below 26°. |
|
|
|
| Alarm Codes | |
|
|
|
|
Message | Cause |
| Solution |
“P1” | Bottle Probe is Unplugged |
| Attach Bottle Probe to Unit |
|
|
| |
Faulty Bottle Probe Connection |
| 1. Check Bottle Probe attachment at circular connector | |
|
| ||
|
|
| 2. Check Bottle Probe connection at green terminal block on |
|
|
| back of controller |
| Defective Bottle Probe |
| Replace the Bottle Probe |
“P2” | Faulty Evaporator Probe |
| Check Evaporator Probe connection at green terminal block on |
| Connection |
| back of controller |
| Defective Evaporator Probe |
| Replace the Evaporator Probe |
“HA” | Defective Bottle Probe |
| Replace the Bottle Probe |
“LA” | The Bottle Probe is sensing a |
| Allow the room to warm up which will increase the temperature |
| temperature of 4° below the set |
| of the wine |
| point |
|
|
| Defective Bottle Probe |
| Replace the Bottle Probe |
“POF” | The keypad is locked |
| Hold “Up” and “Down” buttons for 3 to 5 seconds to disable, |
|
|
| “PON” should appear |
Page 27