VII. OPERATING THE BLAST CHILL CONTROL - SYSPAR

VII. i - ACCESSING SYS PAR SETTING LEVEL:

SYS PAR represents the supervisor level of access to the SmartChill® controller, allowing on-site adjustment to the factory preset operating parameters.

To enter the SYSPAR access level please follow the below procedure.

STEP ONE: From the MAIN MENU, select MORE by pressing the button to the right of where this is shown on the display. The menu shown will then change to display additional menu options.

STEP TWO: Press the button to the right of where SETUP is shown on the display. Note when you first enter SETUP, only Preset Supervisor is available (as delivered, only the factory preset supervisor’s PIN access or ID is set-up).

Press the buttons to the left and right of where PASSWORD is shown on the display to scroll to the factory preset PIN of 57.Press the button to the right of where ENTER appears on the control to enter this PIN number. The SETUP display menu is displayed.

NOTE: If users have already been setup, select the supervisors name using the UP or DOWN keys. On the next line, use the UP or DOWN keys to enter their Password (or Personal Identification Number). Press the button to the right of where ENTER appears on the control to enter this selection. The SETUP display menu is displayed.

STEP THREE: From the SETUP display menu , select the button to the right of where SYS PAR is shown on the display. Refer to the diagram on page 21 in order to access the various Sys Par settings

MAIN MENU

AIR 35°F

BY TEMP

BY PROD

BY TIME

 

 

 

08:05:01

 

 

 

 

 

MORE

MAIN MENU

08:06:01

HOLD PROD

 

PRINT

DEFROST

 

 

 

 

SETUP

BACK

 

 

 

SELECT SUPERVISOR: PRESET SUPERVISORPASSWORD (PIN): 00

CANCEL ENTER

SELECT SUPERVISOR: PRESET SUPERVISORPASSWORD (PIN): 57

CANCEL ENTER

MAIN MENU

08:06:01

HOLD PROD

PRINT

DEFROST

SETUP

BACK

 

SETUP

09:04:11

PRODUCTS

SYS PAR

USERS

 

MAIN MENU

 

SYS PAR: SET CLOCK

ITEM:

MONTH

VALUE:APRIL

CANCEL

ENTER

SYS PAR Menu Display

-20-

Image 21
Contents Important Warranty Notes Introduction Table of ContentsBy Time Type ChillStart Main Menu Blast Chiller Quick Start ChecklistBasic Operating Guidelines II. Receipt Inspection III. InstallationIII. Installation Front IV. Care & Maintenance Reading the Serial TAG OtherVersion VI. the Smartchill Control↓TARGET Temp 0F↑ By TempMain MuteADD/REMOVE Holding AIRChilling AIR ContinueTime ADD 30 Minutes Reset Timer Stop Continue STOP/RESETBy Time Type Chill ↓CYCLE Time Holding↓TIM Smith By Prod↑CHICKEN Parts ↓SOUP Vegetable Chicken PartsBy Product VII. Operating the Blast Chill Control Hold Mode & Defrost MoreDefrost VII. Operating the Blast Chill Control Printing VII. Operating the Blast Chill Control SET UP Products ↓TIM Smith ↑ ↓PASSWORD PIN 07↑ VII. Operating the Blast Chill Control SET UP UsersUsers ADDVII. Operating the Blast Chill Control Syspar ProductsSYS PAR Itemmonth Cancel Enter SYS PAR SET Clock ItemyearCommunicating with Computer Please Wait VIII. Smartchilltm CommunicationsIX. Glossary Replacement Parts List XI. a Food Probe Error During Chill Cycle by Temp XI. Summary of Error MessagesStandard Domestic Warranty XII. Warranty InformationHours of Operation XIII. Mechanical Trouble Shooting Guide