For Non-Vented (recirculating) Installations
If it is not possible to vent cooking fumes and vapors to the outside, the hood can be used in the
Roof Venting | Wall Venting |
|
|
| (recirculating) |
Electrical Requirements
Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in conformance with National Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards
B |
A
A
B
B
A
If codes permit and a separate ground wire is used, it is recommended that a qualified electrician determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA
CSA International
8501 East Pleasant Valley Road
Cleveland, OH
■ | A 120 volt, 60 Hz., AC only, |
| required. |
■ | If the house has aluminum wiring, follow the procedure |
| below: |
A. Roof cap | A. Wall cap | A. Deflector |
B. 6" (15.2 cm) | B. 6" (15.2 cm) | B. 6" (15.2 cm) |
round vent | round vent | round vent |
Calculating Vent System Length
To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.
Vent Piece | 6" (15.2 cm) Round |
45° elbow | 2.5 ft |
| (0.8 m) |
|
|
90° elbow | 5.0 ft |
| (1.5 m) |
Maximum equivalent vent length is 35 ft (10.7 m).
Example vent system
90 elbow |
|
|
|
|
|
| Wall cap | ||
|
| 6 ft (1.8 m) |
|
| |||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2ft
(0.6 m)
The following example falls within the maximum recommended vent length of 35 ft (10.7 m).
1 | - 90° elbow | = 5.0 ft (1.5 m) |
1 | - wall cap | = 0.0 ft (0.0 m) |
8 ft (2.4 m) straight | = 8.0 ft (2.4 m) | |
|
| |
Length of system | = 13.0 ft (3.9 m) | |
|
|
|
1. | Connect a section of solid copper wire to the pigtail |
| leads. |
2. | Connect the aluminum wiring to the added section of |
| copper wire using special connectors and/or tools |
| designed and UL listed for joining copper to aluminum. |
Follow the electrical connector manufacturer's recommended procedure. Aluminum/copper connection must conform with local codes and industry accepted wiring practices.
■Wire sizes and connections must conform with the rating of the appliance as specified on the model/serial rating plate. The model/serial plate is located behind the filter on the rear wall of the range hood.
■Wire sizes must conform to the requirements of the National Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards C22.
6