INSTALLATION
Distance (ft.) | Number of Pipe Supports |
16 | 2 |
32 | 3 |
48 | 5 |
64 | 7 |
80 | 9 |
C.3.1. Installation At The Same Level
If the condensing unit is going to be installed at the same level with the cabinet, follow the instructions in the FIG #5
FIG # 5
C.3.2. Installation At Different Levels
If the remote condensing unit is installed at a higher level than the cabinet (FIG #6) insert a siphon in the return line at every 6 ft. of difference in height. If the remote condensing unit is installed at a lower level than the cabinet (FIG #7) it is not necessary to insert any siphons.
| FIG #6 | FIG #7 |
Insert a siphon at the beginning (a) and at the end (b) of each riser |
| |
|
|
|
C.4. Connect The Remote Unit |
|