American Panel AP24BC250-3 user manual The low food alarm temperature should be left at

Page 17
The low food alarm temperature should be left at

AP24BC250-3, AP24BCF300-3, AP40BC350-3, AP40BCF450-3 Manual

The low food alarm temperature should be left at

35 oF. However, to make a change:

o. To change the temperature, press *YES for shock freezers (AP24BCF300-3, AP40BCF450-3) or NO for blast chillers (AP24BC250-3, AP40BC350-3) and go to step r.

then press The P.C. baud rate should be left at 38400..

INITIAL PROGRAMMING

SOFT & HARD

LOW FOOD ALARM

35 °F

35 Blinks

p. To change to YES or NO, press Manual background or Manual background then

press Manual background.

INITIAL PROGRAMMING

SHOCK FREEZE?

YES *

YES Blinks

*YES for shock freezers (AP24BCF300-3, AP40BCF450-3)

NO for blast chillers (AP24BC250-3, AP40BC350-3) and go to step r.

q. To change the temperature, press Manual background or Manual background

then press Manual background.

INITIAL PROGRAMMING

SHOCK FREEZE

LOW FOOD ALARM

-5 °F

-5 Blinks

r.To change to YES or NO, press Manual background or Manual background then

press Manual background.

INITIAL PROGRAMMING

UV CYCLE?

NO

NO Blinks

s. To change to YES or NO, press Manual background or Manual background then

press Manual background.

INITIAL PROGRAMMING

DEFROST CYCLE?

YES

YES Blinks

INITIAL PROGRAMMING

t. To change to YES or NO, press

or

then

PC CONNECTION?

 

 

 

 

 

 

NO Blinks

 

 

 

 

NO

press

.

 

 

 

 

 

 

For YES, the display will show:

 

 

 

 

 

 

The P.C. baud rate should be left at 38400.

 

INITIAL PROGRAMMING

 

 

 

However, to make a change:

 

 

 

 

 

 

 

 

PC BAUDRATE

 

38400

Blinks

 

 

 

 

 

 

 

 

 

 

u. To change the baud rate, press

or

then

38400

 

 

 

 

 

 

 

press

.

 

 

 

 

 

 

v. To change the number (between 01 & 32), press

 

 

 

INITIAL PROGRAMMING

 

 

 

or

then press

.

 

CHILLER NETWORK ID

 

01 Blinks

 

# 01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INITIAL PROGRAMMING

 

 

 

w.To change to YES or NO, press

or

then

PRINTER CONNECTION?

 

 

 

 

 

 

 

 

NO Blinks

 

 

 

 

NO

 

press

.

 

 

 

 

 

 

16

Image 17
Contents REV. E American Panel CorporationE-mail service@americanpanel.com USER’S MANUALINSTALLATION OF REMOTE UNITS CONTROLLER FEATURESREQUIREMENTS TO BE MET DURING INSTALLATION 8 STEPS INSTALLATION AT THE SAME LEVELMAINTENANCE PREPARING AND USING THE OPTIONAL PRINTERMAINTENANCE AND CLEANING CLEANING THE CONDENSEROPERATING MODES CONTROLLER FEATURESINTRODUCTION PC CONNECTION OPTIONAL OPERATING CYCLESPRINTER OPTIONAL REQUIREMENTS TO BE MET DURING INSTALLATION 8 STEPS INSTALLATION OF REMOTE UNITSINSTALLATION AT THE SAME LEVEL COMPRESSORCONNECTION PIPING FOR REMOTE CONDENSING UNITS INSTALLATION AT DIFFERENT LEVELSINSTALLATION INSTALLATIONDIMENSIONS WARNINGSELECTRICAL AND REFRIGERATION SPECIFICATIONS VERIFYING CORRECT INSTALLATIONCONNECTION TO THE REMOTE UNIT CONDENSATE DRAINAGE CONNECTIONSPACES AROUND THE CABINET STARTING & TESTING THE UNITBLAST CHILLING USING THE HURRICHILL TECHNOLOGYSHOCK FREEZING SOFT CHILL CYCLELOADING PANNING AND LOADINGPANNING CONTROL PANEL FOR MODELS AP24 & AP40 BLAST CHILLERS / SHOCK FREEZERS KEY COMBINATIONS KEYBOARD KEYSON/OFF & START/STOP PROGRAMMING KEYSIf the entered password is wrong the display will show c. Enter the default password by pressing, in order, thePROGRAMMING 1. INITIAL PROGRAMMINGThe high food alarm temperature should be left at The high air alarm temperature should be left atThe low air alarm temperature should be left at The P.C. baud rate should be left at The low food alarm temperature should be left atYES for shock freezers AP24BCF300-3, AP40BCF450-3 NO for blast chillers AP24BC250-3, AP40BC350-3 and go to step r2. PROGRAMMING THE CYCLES AUTOMATIC HARD CYCLE PARAMETERS PROGRAMMING AUTOMATIC SOFT CYCLE PARAMETERS PROGRAMMINGk. To change the temperature, press AUTOMATIC SHOCK CYCLE PARAMETERS PROGRAMMINGthen press p. To change the temperature, pressUV LIGHT CYCLE PARAMETERS PROGRAMMING HEATED PROBE CYCLE PARAMETERS PROGRAMMING DEFROST CYCLE PARAMETERS PROGRAMMINGThe defrost type must be left AIR FLOW aa. Pressgg. Press MANUAL SOFT CYCLE PARAMETERS PROGRAMMINGThe LED for SOFT will be steady hh. To change the temperature, pressMANUAL HARD CYCLE PARAMETERS PROGRAMMING MANUAL SHOCK CYCLE PARAMETERS PROGRAMMING 3. RECIPE NAME PROGRAMMING 1. AUTOMATIC MODE - SOFT CHILL OPERATIONalternating 2. MANUAL MODE - SOFT CHILLalternating with 3. HARD CHILL CYCLE 5. UV STERILIZATION CYCLE 4. SHOCK FREEZE CYCLE6. DEFROST CYCLE a. To perform a UV cycle remove all food, then pressb. Open the door 7. HEATED FOOD PROBEc. Press the defrost cycleOTE To stop any cycle before it has finished, press START/STOP 8. PREPARING AND USING THE OPTIONAL PRINTERNOTE The optional printer is delivered fully installed d. Enter your password, then pressPRINTER 9. TO CLEAR DATALOADING A ROLL OF PAPER MAINTENANCEREMOVING A ROLL OF PAPER OPERATING THE PRINTERREPLACING THE RIBBON WITH PAPER IN THE PRINTER MAINTENANCE AND CLEANINGCLEANING THE CONDENSER CLEANING WIRING DIAGRAMSCOMPARTMENT DO NOT USE ABRASIVES, SOLVENTSAP24BC250-3, AP24BCF300-3, AP40BC350-3, AP40BCF450-3 Manual AP24BC250-3, AP24BCF300-3, AP40BC350-3, AP40BCF450-3 Manual AP24BC250-3, AP24BCF300-3, AP40BC350-3, AP40BCF450-3 Manual COMPUTER CONNECTION DESCRIPTION PARTS LISTPART # installing contractor. It is not covered by this Warranty STANDARD WARRANTYAMERICAN PANEL CORP BLAST CHILLERS / SHOCK FREEZERS ONLYORDERING PRINTER SUPPLIES RIBBON & PAPER