Section 2 — Installation
Guardian 40kW
DANGER
Serious injury or damage may occur if not
!configured properly. Please consult an author- ized service dealer with any questions.
1.13 TORQUE SPECIFICATIONS
Tighten the bolts from the middle out, in a criss- cross pattern.
Cylinder Head | 50 ft.lb./105 ft.lb./105 ft.lb. |
Intake Manifold | 48 in.lb./84 in.lb./84 in.lb. |
Exhaust Manifold | 25 ft.lb. |
Do not use any chromate base rust inhibitor
!with ethylene glycol base
1.14 ENGINE OIL RECOMMENDATIONS
The unit has been filled with
| Temperature | Oil Grade (Recommended) |
|
| Above 80° F (27° C) | SAE |
|
| 32° to 80° F | SAE |
|
| Below 32° F (0° C) | SAE |
|
NOTE:
Synthetic oil is highly recommended in any ele- ment with temperatures above 90° F or below 30° F.
Any attempt to crank or start the engine
!before it has been properly serviced with the recommended oil may result in an engine fail- ure.
1.15 COOLANT RECOMMENDATIONS
Use a mixture of half low silicate ethylene glycol base
1.16 BEFORE INSTALLATION
Before installing this equipment, check the ratings of both the generator and the transfer switch. Read “Emergency Isolation Method” and “Total Circuit Isolation Method” in Sections 2.5 and 2.6.
The generator’s rated wattage/amperage capacity must be adequate to handle all electrical loads that the unit will power. The critical (essential) loads may need to be grouped together and wired into a sepa- rate “emergency” distribution panel.
The standard transfer switch has no sensing or con- trolling circuit boards. Instead, the generator control console houses a “Printed Circuit Board Assembly”, which controls all phases of operation, including engine start up and load transfer.
2.1STANDBY GENERATOR INSTALLATION
DANGER
Connecting this generator to an electrical sys- tem normally supplied by an electric utility shall be by means of a transfer switch, so as to isolate the electric system from the utility distri- bution system when the generator is operating. Failure to isolate the electric system by these means will result in damage to the generator and may also result in injury or death to utility workers due to backfeed of electrical energy.
If an open bottom is used, the
Only qualified, competent installation contractors or electricians thoroughly familiar with applicable codes, standards and regulations should install this standby electric power system. The installation must comply strictly with all codes, standards and regula- tions pertaining to the installation.