System Configuration | |
|
|
Configure Alarms
Use the Config Alarms menu to configure LTU and NTU Interface alarm parameters and the HDSL span alarm parameters. When setting alarm parameters for LTUs and NTUs, keep the following rules in mind:
•Disabled alarms do not cause LED indications and are not stored in history. Console screen menu alarm history reports are not generated.
•Minor alarms cause LED indications and are stored in history. Console screen menu alarm history reports are generated.
•Major alarms cause LED indications, actuate the line unit alarm relay, and are stored in history. Console screen menu alarm history reports are generated.
•The LTU alarm relay activates in response to a major alarm at the LTU only.
•The NTU alarm relay activates in response to a major alarm at the NTU only.
•For the duration of a major alarm, the line unit alarm relay contacts are connected as follows:
–The C (Common) contact is connected to the NO (Normally Open) contact.
–The NC (Normally Closed) contact is floating.
•With no alarm, the C and NC contacts are connected, and the NO contact remains floating.
•The line unit alarm relay operates in a
Type A at the Config
Figure 24. Config Alarms Menu
August 9, 2002 | 41 |