Advantech ADAM-5560 user manual Figure B.10 Double Isolated Cable

Models: ADAM-5560

1 194
Download 194 pages 11.74 Kb
Page 187
Image 187

Figure B.10 Double Isolated Cable

Double isolated cable Figure 10 is an example of a double isolated cable. The first isolating layer of spiraled aluminum foil covers the conductors. The second isolation layer is several bare conductors that spiral and cross over the first shield layer. This spiraled structure makes an isolated layer for reducing external noise. Additionally, follow these tips just for your reference.

The shield of a cable cannot be used for signal ground. The shield is designed for carrying noise, so the environment noise will couple and interfere with your system when you use the shield as signal ground.

The higher the density of the shield - the better, especially for communication network.

Use double isolated cable for communication network / AI / AO.

Both sides of shields should be connected to their frame while inside the device. (for EMI consideration)

Don’t strip off too long of plastic cover for soldering.

Chapter B Grounding Reference

179

ADAM-5560 Series User Manual

Page 187
Image 187
Advantech ADAM-5560 user manual Figure B.10 Double Isolated Cable