2.4System Wiring and Connections

This section provides basic information on wiring the power supply, I/O modules and communication port connection.

2.4.1Power Supply Wiring

Although the ADAM-5560 Series Controller is designed for a standard industrial unregulated 24 VDC power supply, they accept any power unit that supplies within the range of +10 to +30 VDC. The power supply ripple must be limited to 200 mV peak-to- peak, and the immediate ripple voltage should be maintained between +10 and +30 VDC. Screw terminals +Vs and GND are for power supply wiring.

Note! The wires used should be sized at least 2 mm.

Figure 2.11 ADAM-5560 Series Controller Power Wiring

2.4.2I/O Module Wiring

The system uses a plug-in screw terminal block for the interface between I/O mod- ules and field devices. The following information must be considered when connect- ing electrical devices to I/O modules.

1.The terminal block accepts wires from 0.5 mm 2 to 2.5 mm.

2.Always use a continuous length of wire. Do not combine wires to make them longer.

3.Use the shortest possible wire length.\

4.Use wire trays for routing where possible.

5.Avoid running wires near high energy wiring.

6.Avoid running input wiring in close proximity to output wiring where possible.

7.Avoid creating sharp bends in the wires.

2.4.3Connection of Communication Ports

The ADAM-5560 Series Controller has four communication ports. These ports allow you to integrate the remote devices.

ADAM-5560 Series User Manual

26

Page 34
Image 34
Advantech ADAM-5560 user manual System Wiring and Connections, Power Supply Wiring, 2 I/O Module Wiring