Installation 2
Install the shield after you have finished connecting the load wires.
Shield
Load Connections for 80V to 600V Models
| SHOCK HAZARD Hazardous voltages may exist at the outputs and the load |
WARNING | |
| connections when using a power supply with a rated output greater than 40V. |
| To protect personnel against accidental contact with hazardous voltages, |
| ensure that the load and its connections have no accessible live parts. Ensure |
| that the load wiring insulation rating is greater than or equal to the maximum |
| output voltage of the power supply. |
The 80V to 600V models have a
Wire Size: | AWG 18 to AWG 10 |
Stripping Length: | 10 mm (0.39 in.) |
Torque: | 6.5 - 7 |
The following instructions describe how to connect the load wires to the power supply:
•Strip wires back approximately 10 mm (0.39 in).
•Loosen the connector terminal screws and insert the stripped wires into the terminal. Tighten the terminal screw securely.
+V
Positive Output (+)
Negative
Output/Return
Load wires
Series N5700 User’s Guide | 23 |