2 Installation

Setting up the Slave Units

Set the rear panel setup switch SW1 position 2 to it’s up position. Connect J1 pin 10 (Current Program) of the slave unit to J1 pin 25 (Parallel) of the master unit. Also connect a short between J1 pin 8 and J1 pin 12. The output voltage of the slave units should be programmed higher than the output voltage of the master unit to prevent interference with the master unit’s control. The current limit of each unit should be programmed to the desired load current limit divided by the number of parallel units.

Setting the Over-Voltage Protection

The master unit OVP should be programmed to the desired OVP level. The OVP of the slave units should be programmed to a higher value than the master. When the master unit shuts down, it programs the slave unit to zero output voltage. If a slave unit shuts down when its OVP is set lower than the master output voltage, only that unit shuts down and the remaining slave units will supply all the load current.

Setting the Over-Current Protection

 

 

Over-current protection, if desired, may only be used with the master

 

 

unit. When the master unit shuts down, it programs the slave units to

 

 

zero output voltage.

Series Connections

 

 

 

SHOCK HAZARD

 

WARNING

 

 

For models up to 60 VDC rated output, no point on the output shall be more

 

 

than ±60 VDC above or below chassis ground.

 

 

For models greater than 60 VDC rated output, no point on the Positive output

 

 

shall be more than ±600 VDC above or below chassis ground.

 

 

For models greater than 60 VDC rated output, no point on the Negative output

 

 

shall be more than ±400 VDC above or below chassis ground.

 

 

 

 

 

Only power supplies that have identical voltage and current ratings can be

 

CAUTION

 

 

connected in series.

 

 

 

 

 

Two units of the same voltage and current rating can be connected in

 

 

series to provide up to two times the output voltage capability.

 

 

Because the current is the same through each element in a series

 

 

circuit, outputs connected in series must have equivalent current

 

 

ratings. Otherwise, the higher rated output could potentially damage

 

 

the lower rated output by forcing excessive current through it under

 

 

certain load conditions. Refer to the following figures for typical

 

 

series connections using either local or remote sensing.

30

 

Series N5700 User’s Guide

Page 30
Image 30
Agilent Technologies N5700 manual Series Connections, Setting up the Slave Units, Setting the Over-Voltage Protection

N5700 specifications

Agilent Technologies, now part of Keysight Technologies, is renowned for its innovative solutions in electronic measurement and instrumentation. Among its impressive portfolio, the Agilent N5700 series of power supplies stands out, providing precision, reliability, and versatility for a range of applications in test and measurement.

The N5700 series features multiple models, each designed to meet the varying power requirements of test systems and electronic devices. One of its key characteristics is its adjustable output voltage and current, allowing users to set parameters according to specific test needs. With outputs ranging from 0 to 60 V and up to 6 A, the N5700 series caters to both low and high-power applications effectively.

A notable technology integrated into the N5700 series is its advanced measurement capabilities. The built-in voltmeter and ammeter enable real-time monitoring of output voltage and current, ensuring precise control over the power supplied to the device under test. This feature is particularly advantageous in troubleshooting and optimization scenarios, providing engineers with immediate feedback on performance.

The N5700 also embraces the latest in power supply control technology with its intuitive user interface. The front panel incorporates a clear display and simple navigation controls, allowing users to program settings easily and access functions without extensive training. Additionally, remote programming capabilities via GPIB, USB, or LAN facilitate integration into automated test setups, enhancing productivity and efficiency.

Thermal management is another hallmark of the N5700 series. Its design ensures effective heat dissipation, enabling reliable operation even under demanding conditions. This robustness is critical in environments where consistent performance is essential, such as in research laboratories and manufacturing facilities.

Furthermore, safety features are thoughtfully included in the N5700 series, such as overvoltage protection, overcurrent protection, and short-circuit protection. These elements assure users that their devices and test setups remain secure during testing, minimizing the risk of damage.

In summary, the Agilent N5700 series power supplies encapsulate the fusion of precision, advanced measurement technology, user-friendly design, thermal management, and robust safety features. This combination makes them an invaluable tool for engineers and researchers engaged in electronic testing and development across various industries. With its versatility and reliability, the N5700 series continues to play a pivotal role in advancing electronic measurement methodologies.