Appendix A Specifications

Agilent Models N5741A – N5752A and N5761A – N5772A

Model

N5741A

N5742A

N5743A

N5744A

N5745A

N5746A

N5747A

N5748A

N5749A

N5750A

N5751A

N5752A

 

N5761A

N5762A

N5763A

N5764A

N5765A

N5766A

N5767A

N5768A

N5769A

N5770A

N5771A

N5772A

Series and Parallel Capability:

Parallel operation

Up to 4 identical units can be connected in master/slave mode with single–wire current balancing

Series operation

Up to 2 identical units can be connected using external protection diodes

Savable states:

In volatile memory 16 (in memory locations 0-15)

Interface Capabilities:

GPIB

SCPI - 1993, IEEE 488.2 compliant interface

LXI Compliance

Class C (only apples to units with the LXI label on the front panel)

USB 2.0

Requires Agilent IO Library version L.01.01 and up, or 14.0 and up

10/100 LAN

Requires Agilent IO Library version L.01.01 and up, or 14.0 and up

Environmental Conditions:

Environment

Indoor use, installation category II (AC input), pollution degree 2

Operating temp.

0°C to 40°C @ 100% load

Storage temp.

–20°C to 70°C

Operating humidity

30% to 90% relative humidity (no condensation)

Storage humidity

10% to 95% relative humidity (no condensation)

Altitude

Up to 3000 meters.

 

Above 2000m, derate the output current by 2%/100m and derate the maximum ambient temperature by 1°C/100m.

 

(For 1500W models from 60V to 600V, derate either the output current or the ambient temperature, but not both.)

LED statement

Any LEDs used in this product are Class 1 LEDs as per IEC 825-1

Regulatory Compliance:

EMC

Complies with the European EMC directive 89/336/EEC for Class A test and measurement products.

 

Complies with the Australian standard and carries the C-Tick mark.

 

This ISM device complies with Canadian ICES-001. Cet appareil ISM est conforme à la norme NMB-001 du Canada.

 

Electrostatic discharges >1kV near the I/O connectors may cause the unit to reset and require operator intervention.

Safety

Complies with the European Low Voltage Directive 73/23/EEC and carries the CE-marking.

 

Complies with the US and Canadian safety standards for test and measurement products.

Acoustic Noise Declaration:

Statements provided to comply with requirements of the German Sound Emission Directive, from 18 January 1991: Sound Pressure Lp <70 dB(A), * At Operator Position, * Normal Operation, * According to EN 27779 (Type Test). Schalldruckpegel Lp <70 dB(A) * Am Arbeitsplatz, * Normaler Betrieb, * Nach EN 27779 (Typprüfung).

Output Terminal Isolation:

6V to 60V units

No output terminal may be more than +/- 60 VDC from any other terminal or chassis ground

80V to 600V units

No output terminal may be more than +/- 600 VDC from any other terminal or chassis ground

AC Input:

Nominal Input

100 – 240 VAC; 50/60Hz

Input Current 750W

10.5A @ 100 VAC nominal; 5A @ 200 VAC nominal

Input Current 1500W

21A @ 100 VAC nominal; 11A @ 200 VAC nominal

Input Range

85 – 265 VAC; 47 – 63 Hz.

Power Factor

0.99 at nominal input and rated output power

Efficiency

76% – 87% for 750W units; 77% – 88% for 1500W units

Inrush Current

< 25A for 750W units; < 50 A for 1500W units

90

Series N5700 User’s Guide

Page 90
Image 90
Agilent Technologies N5700 Series and Parallel Capability, Savable states, Interface Capabilities, Regulatory Compliance

N5700 specifications

Agilent Technologies, now part of Keysight Technologies, is renowned for its innovative solutions in electronic measurement and instrumentation. Among its impressive portfolio, the Agilent N5700 series of power supplies stands out, providing precision, reliability, and versatility for a range of applications in test and measurement.

The N5700 series features multiple models, each designed to meet the varying power requirements of test systems and electronic devices. One of its key characteristics is its adjustable output voltage and current, allowing users to set parameters according to specific test needs. With outputs ranging from 0 to 60 V and up to 6 A, the N5700 series caters to both low and high-power applications effectively.

A notable technology integrated into the N5700 series is its advanced measurement capabilities. The built-in voltmeter and ammeter enable real-time monitoring of output voltage and current, ensuring precise control over the power supplied to the device under test. This feature is particularly advantageous in troubleshooting and optimization scenarios, providing engineers with immediate feedback on performance.

The N5700 also embraces the latest in power supply control technology with its intuitive user interface. The front panel incorporates a clear display and simple navigation controls, allowing users to program settings easily and access functions without extensive training. Additionally, remote programming capabilities via GPIB, USB, or LAN facilitate integration into automated test setups, enhancing productivity and efficiency.

Thermal management is another hallmark of the N5700 series. Its design ensures effective heat dissipation, enabling reliable operation even under demanding conditions. This robustness is critical in environments where consistent performance is essential, such as in research laboratories and manufacturing facilities.

Furthermore, safety features are thoughtfully included in the N5700 series, such as overvoltage protection, overcurrent protection, and short-circuit protection. These elements assure users that their devices and test setups remain secure during testing, minimizing the risk of damage.

In summary, the Agilent N5700 series power supplies encapsulate the fusion of precision, advanced measurement technology, user-friendly design, thermal management, and robust safety features. This combination makes them an invaluable tool for engineers and researchers engaged in electronic testing and development across various industries. With its versatility and reliability, the N5700 series continues to play a pivotal role in advancing electronic measurement methodologies.