Duct Flange Cut Outs

CUT USING TIN SNIPS

PRESS OUT BY HAND

CUT FOUR CORNERS

AFTER REMOVING SHEET

METAL

SCRIBE LINES OUTLINING

DUCT FLANGES

Duct Flange Cut Outs

When the furnace is used in connection with a cooling unit, the furnace should be installed in parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element. With a parallel flow arrangement, the dampers or other means used to control the flow of air must be adequate to prevent chilled air from entering the furnace and, if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool position.

When the furnace is installed without a cooling coil, it is recom- mended that a removable access panel be provided in the outlet air duct. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for visual light inspection or such that a sampling probe can be inserted into the airstream. The access panel must be made to prevent air leaks when the furnace is in operation.

When the furnace is heating, the temperature of the return air enter- ing the furnace must be between 55°F and 100°F.

FILTERS - READ THIS SECTION BEFORE INSTALLING THE RETURN AIR DUCTWORK

Filters must be used with this furnace. Discuss filter maintenance with the building owner. Filters do not ship with this furnace, but must be provided by the installer. Filters must comply with UL900 or CAN/ULCS111 standards. If the furnace is installed without fil- ters, the warranty will be voided.

On upflow units, guide dimples locate the side return cutout locations. Use a straight edge to scribe lines connecting the dimples. Cut out the opening on these lines. NOTE: An undersized opening will cause reduced airflow.

Refer to Minimum Filter Area tables to determine filter area require- ments.

 

 

 

 

 

 

 

UPFLOW

 

 

 

 

 

 

 

COOLING AIRFLOW REQUIREMENT (CFM)

 

 

600

 

800

 

1000

 

1200

 

1400

 

1600

 

2000

 

 

 

 

 

 

 

 

AirflowInput

0453__XA

376*

 

384

 

480

 

576

 

---

 

---

 

---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0704__XA

---

 

---

 

627*

 

627*

 

672

 

768

 

---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0905__XA

---

 

---

 

---

 

836*

 

836*

 

836*

 

960

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1155__XA

---

 

---

 

---

 

940*

 

940*

 

940*

 

960

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COUNTERFLOW

 

 

 

 

 

 

 

COOLING AIRFLOW REQUIREMENT (CFM)

 

 

600

 

800

 

1000

 

1200

 

1400

 

1600

 

2000

 

 

 

 

 

 

 

 

Input Airflow

0704__XA

---

 

---

 

320*

 

320*

 

336

 

384

 

---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0905__XA

---

 

---

 

---

 

427*

 

427*

 

427*

 

480

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Minimum filter area dictated by heating airflow requirement.

Permanent Minimum Filter Area (sq. in)

[Based on a 600 ft/min filter face velocity]

 

 

 

 

 

UPFLOW

 

 

 

 

 

COOLING AIRFLOW REQUIREMENT (CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

600

800

1000

 

1200

 

1400

1600

2000

 

 

 

 

 

 

 

 

 

 

 

AirflowInput

0453__XA

376*

384

480

 

576

 

---

---

---

 

 

 

 

 

 

 

 

 

 

0704__XA

---

---

564*

 

564*

 

672

768

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0905__XA

---

---

---

 

752*

 

752*

768

960

 

 

 

 

 

 

 

 

 

 

 

 

1155__XA

---

---

---

 

940*

 

940*

940*

960

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COUNTERFLOW

 

 

 

 

 

 

COOLING AIRFLOW REQUIREMENT (CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

600

 

800

1000

1200

1400

1600

2000

 

 

 

 

 

 

 

 

 

 

 

Input Airflow

0905__XA

---

 

---

---

854*

854*

854*

960

 

0704__XA

---

 

---

641*

641*

672

768

---

 

 

 

 

 

 

 

 

 

 

 

*Minimum filter area dictated by heating airflow requirement.

Disposable Minimum Filter area (sq. in) [Based on 300 ft/min filter face velocity]

UPRIGHT INSTALLATIONS

Depending on the installation and/or customer preference, differ- ing filter arrangements can be applied. Filters can be installed in the central return register or a side panel external filter rack kit (upflows). As an alternative a media air filter or electronic air cleaner can be used as the requested filter.

The following figure shows possible filter locations.

27

Page 27
Image 27
Amana ACV9, AMV9 Duct Flange Cut Outs, Permanent Minimum Filter Area sq. in, Based on a 600 ft/min filter face velocity