PDU Display Interface

Alarm Relay Map

Configure the relay outputs, using

 

 

 

 

 

 

Alarm Map: 01 of 04

 

 

the Alarm Relay Map. Each

 

 

 

 

 

 

[Vo, By, C4]

 

 

Alarm Map corresponds to an

 

 

Map: Input Voltage

 

 

 

 

 

 

relay output. For example, Alarm

 

 

Apply Now

 

 

 

 

 

 

 

 

 

 

 

 

Map 01of04 corresponds to the first of four relay outputs. The second

 

line, in brackets [ ], lists the items that you have selected to map to the

 

selected relay. The third line allows you to select the alarms to which

 

you want to map the relay:

 

 

 

 

Any Load (L)—Maps to over- or under-current alarms for circuit breaker panels and branch circuits.

Overload (O)—Maps to over-current alarms for circuit breaker panels, branch circuits, and SYSGND

Input Voltage (Vi)—Maps to any input voltage alarm.

Output Voltage (Vo)—Maps to any output voltage alarm.

PDU in Bypass (By)—Not used on this model PDU.

Any Breaker (Br)—Not used on this PDU.

Contacts 1–4(C1,C2,C3,C4)—Maps to the input contact alarms.

Before exiting the screen, to save your changes, select the Apply

Now option on the bottom line of the screen.

60 kW InfraStruXure PDU — Operation and Configuration

19