Customizing and Updating the PDU

6.From the Control Console menu, select System, then Tools, then File Transfer, then

XMODEM.

7.The system will prompt you with Perform transfer with XMODEM -CRC? Type Yes and press ENTER.

8.The system will then prompt you to choose a transfer rate and to change your terminal settings to match the transfer rate. Press ENTER to set the PDU to accept the download.

9.In the terminal program, send the file using XMODEM protocol. Upon completion of the transfer, the console will prompt you to restore the baud rate to normal.

Do not interrupt the download.

Caution

The PDU network management interface will reboot when the download is complete.

58

60 kW InfraStruXure PDU — Operation and Configuration

Page 66
Image 66
American Power Conversion PD60L6FK1, PD60G6FK1, PD60F6FK1, PDRPPNX10 manual Xmodem