Customizing and Updating the PDU

4.If the test was successful, place the Arm/Test switch back to the Arm position. The PDU display interface will clear the EPO test mode alarm. If the test was not successful, see the troubleshooting chart:

Problem

Action

 

 

Neither state LED was red when EPO

• Check the wiring to your EPO switch.

switch was engaged.

• Check to make sure your EPO DIP switch

 

configuration is correct for your switch (NO

 

or NC).

 

 

Only one of the state LEDs was red

• Check to make sure the EPO DIP switch

when the EPO switch was engaged.

configuration is correct for your switch (NO

 

or NC) and test again.

 

• If the switch is configured correctly and

 

both LEDs are not red after testing again,

 

contact customer support at a number on the

 

back cover of this manual.

 

 

5.Repeat this test for each EPO switch installed.

6.Ensure that the Arm/Test rocker switch is in the Arm position on the monitoring unit.

Safety warnings

Hazardous voltage from the branch circuit must be isolated from the 24VAC, 24VDC, and contact closure. 24VAC and 24VDC are considered Class 2 circuits as defined in Article 725 of the National Electrical Code (NFPA 70) and Section 16 of the Canadian Electrical Code (C22.1).

A Class 2 circuit is a source having limited voltage and energy capacity as follows:

a.If an Inherently Limited Power Source, voltage and energy are limited to less than 30VAC, less than 30VDC, and 8A.

b.If not an Inherently Limited Power Source, voltage and energy are limited to less than 30VAC, less than 60VDC, 250VA, and the current is limited to 1000/Vmax. The fuse is limited to 5A if less than 20VAC or 20VDC, or 100/Vmaximum if less than 30VAC or 60VDC.

60 kW InfraStruXure PDU — Operation and Configuration

55

Page 63
Image 63
American Power Conversion PDRPPNX10, PD60G6FK1, PD60F6FK1, PD60L6FK1 manual Safety warnings