PDU Display Interface

Alarm Setup

Use this option of the Alarms screen to access the following options:

Loading Limits

Configure the following in amps and as a percentage of full load:

 

Out High: The upper limit for output current.

 

Out Low: The lower limit for output current.

 

Out Neut: The upper limit for current on the neutral wire for

 

 

the output phases.

Voltage Limits

Configure the following as a percentage under or over the rated

 

voltage:

 

Input: The allowed range for input voltage.

 

Output: The allowed range for output voltage.

Other Limits

Configure these limits:

 

 

Frequency: The frequency variation, in hertz, that is acceptable

 

 

for the output current.

Global Alarm

Set all the loading limits or all the voltage limits simultaneously as a

Config

percentage of full load:

 

Load Limits: Set the same percentage for the upper limit for

 

 

output current, the lower limit for output current, and the upper

 

 

limit for current on the neutral wire for the output phases. (Use

 

 

the Loading Limits option to set these thresholds individually).

Volt Limits: Set the same percentage for the high and low thresholds for input and output voltage. (Use the Voltage Limits option to set these thresholds individually.)

Select Apply Now and then YES to implement your changes.

Alarm Beeper

Use this option of the Alarms screen to turn the alarm beeper ON or OFF.

60 kW InfraStruXure PDU — Operation and Configuration