How to Test the EPO Switch

APC offers an optional InfraStruXure EPO System (EPW9). Contact your APC sales representative, or visit the APC Web site (www.apc.com) for more information.

Note

After a certified electrician has connected an EPO switch to the PDU monitoring unit by way of the user connection plate, you can easily test the switch to make sure it is wired and working properly. The illustration to the right shows the EPO functions on the front panel of the PDU monitoring unit.

EPO DIP switches configure the EPO input for the type of EPO switch that is connected—Normally Open (NO) or Normally Closed (NC).

 

 

T RIPP E D

 

 

 

A RM E D

P O

 

 

E

T E ST

 

 

 

N C

 

N O

 

 

When the EPO Arm/Test rocker is in the Test position, engaging the EPO switch will not cause the load to be powered off. When the rocker is in the Armed position, engaging the

EPO switch will cause the PDU’s Main Input switch to be switched OFF.

The EPO Armed LED is green when the rocker is in the Armed position. The LED is dark

when the rocker is in the Test position.

The EPO Tripped LED is red when the EPO switch is engaged (the EPO button is pressed), regardless of the state of the EPO Arm/Test rocker.

To test your EPO wiring and switches:

1.Place the Arm/Test switch in the Test position. The Armed LED will be dark and the PDU display interface will show the following alarm (in addition to any other active alarms):

Active Alarm xxofxx

EPO Ready To Test

2.Engage the EPO switch. (If your switch is momentary, engage it with one person watching the EPO state LEDs, and another at the EPO switch.)

3.Observe the EPO LEDs. If the switch is wired and working properly, when the switch is engaged, the Tripped LED is red.

54

60 kW InfraStruXure PDU — Operation and Configuration

Page 62
Image 62
American Power Conversion PD60L6FK1, PD60G6FK1, PD60F6FK1 How to Test the EPO Switch, To test your EPO wiring and switches