American Water Heater ITCE3-52/80/119, STCE3-52/80/119 manual Contactor Coil Voltage - At Contactor

Models: ITCE3-52/80/119 COMMERCIAL ELECTRIC WATER HEATERS STCE3-52/80/119

1 76
Download 76 pages 3.39 Kb
Page 34
Image 34
Contactor Coil Voltage - At Contactor

OPERATION & SERVICE

Contactor Coil Voltage - At Contactor

This test procedure will measure contactor coil voltage at the contactor.

1Ensure tank temperature is less than 100°F/38°C - dump water to lower tank temperature if necessary.

2Adjust the temperature settings to ensure a call heat is active for all heating elements. Raise the Operating Set Point in the Temperatures Menu to 140°F or higher. Set all Heating Element Bank Differentials in the Temperatures Menu to 2°F - see pages 52 and 53.

3Using an AC volt meter; set the volt meter to an AC voltage range just above 120 VAC.

4Touch the two volt meter probes to the contactor coil wiring terminals at each contactor. There should be approximately 120 volts present between the two terminals. If there is no voltage proceed to the Contactor Coil Voltage - At CCB test on page 33.

Service Warning: Be extremely careful when performing this test procedure; volt meter probes are routed between wires in tight proximity - there will be high voltage present at all terminals and wiring to the contactors.

5If the measured voltage is considerably less than 120 volts and/or the contactors chatter (open and close rapidly) ensure the Control Circuit Transformer is wired correctly - see page 34.

6If the measured voltage is approximately 120 volts the contactor should close it’s switch contacts. If the contacts are closed the contactor coil is operating properly.

7If the measured voltage is approximately 120 volts and the contactor’s switch contacts do not close - the contactor is defective and must be replaced. When replacing a contactor that has failed in this way check all wiring between the contactor coil and the J4 wiring terminals on the CCB (see pages 42 and 43) for pinched or shorted wires - repair or replace damaged wiring as necessary.

Service Note: A continuity test can also be performed on contactor coils to determine if the failure is due to an open coil winding. Secure power to the water heater at the main breaker or disconnect switch, disconnect both wires to the contactor coil and check for continuity between the two terminals using an ohm meter. If a contactor has an open coil the contactor must be replaced. Check all wiring between the contactor coil and the J4 wiring terminals on the CCB (see pages 42 and 43) for pinched or shorted wires - repair or replace damaged wiring as necessary.

3 Pole Contactor Side View

Electromagnetic

Contactor Coil Wiring

Terminals 120 VAC

Servicing should only be performed by a Qualified Service Agent

32

Page 34
Image 34
American Water Heater ITCE3-52/80/119, STCE3-52/80/119 manual Contactor Coil Voltage - At Contactor