American Water Heater COMMERCIAL ELECTRIC WATER HEATERS manual Temperature Sensor DC Voltage Test

Models: ITCE3-52/80/119 COMMERCIAL ELECTRIC WATER HEATERS STCE3-52/80/119

1 76
Download 76 pages 3.39 Kb
Page 41
Image 41
Temperature Sensor DC Voltage Test

OPERATION & SERVICE

Temperature Sensor DC Voltage Test

1Ensure the main breaker or disconnect switch is turned on.

2Verify the CCB circuit board has the correct input voltage at the J2 socket and is properly grounded - perform the “Checking Power and Ground To The CCB” tests on page 46.

3Unplug the J5 plug from the CCB circuit board (note: the control system will lock out and display “Temp Probe Open” Fault message on the UIM when the J5 plug is removed - cycle power off and reinstall J5 plug when tests are complete). Using a “DC” (direct current) volt meter check for DC voltage between pins 2 & 3 of the J5 socket as shown in the “DC Voltage To Temperature Sensor” image below.

If the measured voltage is 5 VDC the temperature sensor is being powered correctly. If there is not 5 VDC call the toll free Technical Support phone number listed on the back cover of this manual for further assistance.

ECO Continuity Test

1Secure power to the water heater at the main breaker or disconnect switch.

2Unplug the J5 plug from the CCB circuit board - see page 42 for location.

3Ensure tank temperature is less than 100°F/38°C - dump water to lower tank temperature if necessary.

4Using an ohm meter; set the Ohm meter to it’s lowest resistance range (< 200) or to an audible beep continuity test setting if so equipped.

5Touch the ohm meter probes between the two outside pins (red wires) of the J5 plug end as shown in the “Checking ECO Switch Continuity” image below.

If the ohm meter shows continuity (closed circuit) between the two outside pins (red wires) of the J5 plug end the ECO switch has reset properly. If the control system continues to lock out displaying the “Energy Cut Out (ECO)” Fault message with continuity through the ECO present call the toll free Technical Support phone number listed on the back cover of this manual for further assistance.

If the ohm meter shows no continuity (open circuit) between the two outside pins (red wires) of the J5 plug end and the control system and the tank temperature is known to be at or below 100°F/38°C - replace the Immersion Temperature Probe. Secure power to the water heater and drain the water heater before replacing the probe.

If the control system continues to lock out displaying the “Energy Cut Out (ECO)” Fault message and the water temperature inside the water heater is becoming excessive (at or above 202°F/94°C) check contactors (pages 29 - 32) to ensure they are not stuck closed and check for voltage at all heating elements (page 24) during the standby mode. Check water system piping; ensure heat is not being added to the water inside the water heater being serviced by any other heating appliances or heat sources. If all these tests have been performed and the control system continues to lock out displaying the “Energy Cut Out (ECO)” Fault message call the toll free Technical Support phone number listed on the back cover of this manual for further assistance.

DC Voltage To Temperature Sensor

Checking ECO Switch Continuity

 

 

 

 

 

 

 

 

 

 

Servicing should only be performed by a Qualified Service Agent

39

Page 41
Image 41
American Water Heater COMMERCIAL ELECTRIC WATER HEATERS manual Temperature Sensor DC Voltage Test, ECO Continuity Test