6.0 UPS Monitoring

6.0 UPS Monitoring

6.4 Computer interface port

The computer i terface port is diagramed below. Those with technical abilities wishing to use this port in a special application should be aware of the following limitations and capabilities of the interface.

Outputs at Pins 3, 5, and 6 are open-collector outputs which must be pulled up to a common referenced supply no greater than +40 Vdc. The transistors are capable of a maximum noninductive load of 25 mAdc. Use only Pin 4 as the common.

The output at Pin 2 generates a low-to-high RS-232 level when the output load transfers to UPS battery power. The pin is normally at a low RS-232 level.

When on-battery, the UPS shuts down (after a delay) when a high RS-232 level is applied to Pin 1 for 4.5 seconds.

An unregulated +24 Vdc appears at Pin 8 of the interface port whenever the UPS is powered. The supply is limited to 40 mAdc maximum.

Applying a momentary (approx. 1 sec.) high RS-232 level to Pin 7 turns the UPS on. A momentary low RS-232 level turns the UPS off. Pin 7 should be normally unconnected.