![](/images/new-backgrounds/1018068/1806865x1.webp)
7.0Difficulty
7.1Troubleshooting
PROBLEM: | UPS will not turn on |
|
|
Possible cause: | UPS Enable switch is in the off position or the power |
| on switch is not pressed. |
Solution: | Turn on the rear panel UPS Enable switch. Press front- |
| panel power on switch to energize UPS and loads. |
|
|
Possible cause: | UPS’s circuit breaker is tripped (button is extended). |
Solution: | Reduce the UPS’s load by unplugging equipment and |
| reset the circuit breaker (press button on rear panel). |
|
|
Possible cause: | Very low utility voltage or dead outlet. |
Solution: | Check outlet with a table lamp. If very dim, have |
| utility voltage checked by an electrician. |
PROBLEM: | UPS operates |
| voltage is thought to exist. |
|
|
Possible cause: | UPS’s circuit breaker is tripped (button is extended). |
Solution: | Unplug equipment to reduce the UPS’s load. Press the |
| button on the rear panel to reset circuit breaker. |
Possible cause: | Very high, low, or |
Solution: | Test the input voltage with UPS’s line voltage bar |
| graph (see Sec. 5.3). Inexpensive fuel powered |
| generators can cause distorted line |
| Option Switch 1 to the on ( I ) position. |
|
|
PROBLEM: | UPS “beeps” occasionally. |
|
|
Possible cause: | This is normal; the UPS is protecting your computer |
| equipment from momentary sags or swells. |
|
|
PROBLEM: | UPS beeps more than once or twice an hour. |
Possible cause: | Chronically high or distorted line voltage. |
Solution: | Set Option Switches 1 and 2 to match input voltage |
| range. Alternatively, set Option Switch 3 to the on ( I ) |
| position (see Sec. 5.5). |
|
|
31