
7.0Difficulty
7.1Troubleshooting (continued)
| PROBLEM: | UPS does not provide expected back up time. | 
| 
 | 
 | 
| Possible cause: | UPS’s battery is weak from recent outage or wear. | 
| Solution: | The battery needs recharging after an extended | 
| 
 | outage. The battery wears faster when put into service | 
| 
 | often and when used at higher temperatures. | 
| 
 | 
 | 
| Possible cause: | UPS is overloaded. | 
| Solution: | Check load using UPS’s output power bar graph (see | 
| 
 | Sec. 5.2). Unplug  | 
| 
 | 
 | 
| PROBLEM: | Indicators on front panel flash in a “marquee” fashion. | 
| 
 | 
 | 
| Possible cause: | UPS has been shut down by computer software. | 
| Solution: | UPS will restart when AC power returns. | 
| 
 | 
 | 
| PROBLEM: | All indicators are lit and UPS emits constant tone. | 
| 
 | 
 | 
| Possible cause: | Internal UPS fault. | 
| Solution: | Do not attempt to use UPS. Turn off UPS and have it | 
| 
 | serviced immediately. | 
| 
 | 
 | 
| PROBLEM: | Site wiring fault light is  | 
| 
 | 
 | 
| Possible cause: | Building wiring error such as missing ground or hot- | 
| 
 | neutral reversal. | 
| Solution: | A qualified electrician should be summoned to correct | 
| 
 | the building wiring. | 
| 
 | 
 | 
| PROBLEM: | Replace Battery indicator is lit. | 
| 
 | 
 | 
| Possible cause: | Weak battery. | 
| Solution: | Allow the battery to recharge for at least 8 hours. If | 
| 
 | the problem persists after recharging, the battery | 
| 
 | should be replaced. | 
| 
 | 
 | 
32
