MX28B-1200 PRODUCT MANUAL
4.5AC Input Power
Each rectifier requires 208/220/240V ac, single- phase, 50/60 Hz, supplied through an external 20- amp
4.6Battery connections
Battery connections are made at the top rear of the unit. The
A battery disconnect breaker is required external to this equipment. The power plant can monitor auxiliary contacts from this breaker. Battery temperature compensation is available. APC’s master control unit, in conjunction with the optional temperature monitor sensor cable, is used to implement this function.
Revision B
+
-
Battery
Connections
AC entry and vertical wiring channel
4.7DC Distribution
A standard power distribution module within the power box frame contains two
The load return cables for each circuit breaker section connect to a return bus directly opposite the circuit breakers. These return buses contain patterns for 28
Figure 4-3 Power Entry Box and Battery
Connections
Circuit Breaker Positions
Load Returns (+) and
Facility Main Ground Bus
Figure 4-4 DC Distribution