Fuse holders that accommodate telecom fuses are located in a separate fuse power distribution box frame. The fuse holders are designed to hold Bussmann® (or equivalent) TPL-series fuses in sizes of 70 amps to 600 amps. The following stock sizes are available from APC:

FUSE

APC PART

RATING

NUMBER

 

 

200 A

FFA-0106

 

 

300 A

FFA-0093

 

 

600 A

FFA-0099

 

 

Table 5-5 Telecom Power Fuses

5.8.2 Installation of Circuit Breakers and Fuses

5.8.2.1Plug-in Circuit Breakers

1)Remove the circuit breaker cover panel and the plastic cover(s) from the desired location(s).

2)Install the circuit breaker(s) by snapping the top terminal onto the upper bus bar and rotating the unit down until the second terminal snaps onto the breaker termination post as shown in Figure 5-9. The breaker alarm terminals are designed to make contact with the alarm terminal board as the breaker is snapped into place.

NOTE: Circuit breaker alarm contacts close when the circuit breaker is tripped but not when it is turned OFF.

***** CAUTION *****

During circuit breaker installation, carefully align the breaker alarm terminals with the alarm terminal board to avoid breaker terminal damage.

3) Reattach the circuit breaker cover panel.