Revision B |
|
STATUS ALARMS
SYSTEM MODULES BATT PIN OEM
Figure 5-11 Control Unit Display
5.10.2 System Parameters Verification/Adjustment
The MX28B system control unit is delivered with
1)Battery Float Voltage - default =
2)Battery Maximum Recharge Rate - default = 50A. (Bellcore specifications recommend a maximum charging rate of battery capacity (in
3)System Voltage - measurement ≅
4)LVD Option - default = “Enable” (If the MX28B does not have an LVD installed, this should be changed to “Disable”.)
5)Rectifier Information - Check the rectifier information displays to verify that all rectifiers installed can be viewed on the control unit display and that no rectifier alarms are active.
Section 6 provides location information for these parameters and how to make changes if required.
5.10.3 Full System Power Up
To complete a full system power up, perform the following steps
1)Turn OFF all the circuit breakers that supply ac power to the rectifiers in the MX28B dc power plant.
2)Turn on the external circuit breaker from the battery to the power plant.
3)Turn on all the circuit breakers that supply ac power to the rectifiers in the MX28B dc power plant.
4)Load circuit breakers and distribution fusses may now be turned on and inserted as required.
29 |