(Table 6-1. Parameter Locations, Descriptions, and Default Values)

 

 

 

 

 

PARAMETER

DESCRIPTION

DISPLAY SCREENS /

 

 

DEFAULT SETTINGS

Output Relay Major Alias {1}

An alternate name (alias) can be assigned to the relay if

Relay Major

m+

[SYSTEM/OUT-RLY/ALIAS]

desired.

Major

 

 

 

 

 

 

 

 

 

Output Relay 1 Delay {1}

Delay between sensing of the alarm condition and activation

Out-Rly 1 Dly m+

[SYSTEM/OUT-RLY/RLY-MAP]

of the alarm relay. An alarm condition must exist for longer

 

0 sec

 

than the delay to be activated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Relay 6 Delay {1}

Delay between sensing of the alarm condition and activation

Out-Rly 6 Dly m+

[SYSTEM/OUT-RLY/RLY-MAP]

of the alarm relay. An alarm condition must exist for longer

 

0 sec

 

than the delay to be activated.

 

 

 

 

 

 

 

 

 

 

Output Relay Alarms

 

 

 

 

 

 

 

Output Relay 1 {1}

Output Relay 1 alarm can be “mapped” to activate other

Out-Rly 1 Alm m+

[SYSTEM/OUT-RLY/RLY-MAP]

output relays (“Ignore” activates no additional relays).

 

Ignore

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Relay 6 {1}

Output Relay 6 alarm can be “mapped” to activate other

Out-Rly 6 Alm m+

[SYSTEM/OUT-RLY/RLY-MAP]

output relays (“Ignore” activates no additional relays).

 

Ignore

 

 

 

 

 

 

 

 

 

 

LVD SETUP

 

 

 

 

 

 

 

 

LVD1 Trip {1}

LVD1 trip (disconnect) threshold voltage.

LVD1 Trip

m+

[MODULES/LVD/PARAM]

 

 

-42.00 V

 

 

 

 

 

 

 

LVD1 Restore {1}

LVD1 restore (reconnect) threshold voltage.

LVD1 Reset

m+

[MODULES/LVD/PARAM]

 

 

-48.00 V

 

 

 

 

 

 

 

LVD2 Trip {1}

LVD2 trip (disconnect) threshold voltage.

LVD2 Trip

m+

[MODULES/LVD/PARAM]

 

 

-42.00 V

 

 

 

 

 

 

 

LVD2 Restore {1}

LVD2 restore (reconnect) threshold voltage.

LVD2 Reset

m+

[MODULES/LVD/PARAM]

 

 

-48.00 V

 

 

 

 

 

 

 

 

LVD Alarm

 

 

 

 

 

 

 

 

 

LVD1 Option {1}

Set to “Enable” if the unit has an LVD1.

LVD1

Option

m+

[MODULES/LVD/SET-ALM]

 

 

Enable

 

 

 

 

 

 

 

 

LVD1 Alarm {1}

Sets the priority or “mapping” of an LVD1 Alarm.

LVD1 Open Alm m+

[MODULES/LVD/SET-ALM]

 

 

Minor

 

 

 

 

 

 

 

 

 

 

LVD2 Option {1}

Set to “Enable” if the unit has an LVD2.

LVD2

Option

m+

[MODULES/LVD/SET-ALM]

 

 

Enable

 

 

 

 

 

 

 

 

LVD2 Alarm {1}

Sets the priority or “mapping” of an LVD2 Alarm.

LVD2 Open Alm m+

[MODULES/LVD/SET-ALM]

 

 

Minor

 

 

 

 

 

 

 

 

 

 