Revision B

MX28B-1200 PRODUCT MANUAL

distribution section with the front cover removed.

Alternate circuit breaker configurations are available in order for the power frames to provide support for larger individual load connections. Six circuit breakers in the 100 amp to 400 amp range or four circuit breakers in the 225 to 700 amp range in a panel-mount arrangement can be specified instead of the distribution module with 48 plug-in breakers.

Optional power distribution box frames can be added to a power system to support additional circuit breakers or telecom fuses. Auxiliary alarm contacts from circuit breakers can be brought back to the control unit through the use of an alarm extension printed circuit board in each bay. Ten fuses outputs can also be directly monitored by the control unit.

4.8 Environmental

 

 

Ambient Temperature:

-20°C to +65°C operating

 

 

-40°C to +85°C storage

Humidity:

0% to 85%

RH non-condensing operating

 

 

0% to 95%

RH non-condensing storage

Altitude:

Up to 3000m, operating

 

 

Up to 10,000m, storage

4.9 Mechanical

 

Weight:

Base Power Frame – 400 to 600 lbs. (181 to 272 kg)

 

 

Extension Power Frame – 400 to 600 lbs. (181 to 272 kg)

 

 

Rectifier - 11 lbs. (5 kg.)

Dimensions

Box Frame: 84” high x 26” wide x 26” deep

 

 

(2134 mm x 660 mm x 660 mm)

Color:

Dawn Gray (fronts)

4.10 Compliance

 

• Safety

UL 1950

MX28B-1200/2400

11

Page 17
Image 17
APC MX28B-1200, MX28B-2400 manual Environmental, Mechanical, Compliance