Revision B

 

MX28B-1200

PRODUCT MANUAL

 

(Table 6-1. Parameter Locations, Descriptions, and Default Values)

 

 

 

 

 

 

PARAMETER

 

DESCRIPTION

 

DISPLAY SCREENS /

 

 

 

 

DEFAULT SETTINGS

System Low Temperature

{1}

The control unit temperature is below the low temperature

 

Sys LT Alm

m+

[SYSTEM/SET-ALM]

 

threshold.

 

Minor

 

 

 

 

 

 

 

 

 

 

 

Rectifier Configuration {1}

The rectifier configuration differs from its stored

 

Rect Cfg Alm

m+

[SYSTEM/SET-ALM]

 

configuration.

 

Minor

 

 

 

 

 

 

 

 

 

 

 

Rectifier Fail 1-of-N {1}

 

Rectifier Fail 1-of-N alarm - one rectifier has at least one

 

Rect 1ofN Alm m+

[SYSTEM/SET-ALM]

 

alarm condition.

 

Minor

 

 

 

 

 

 

 

 

 

 

 

Rectifier Fail 2-of-N {1}

 

Rectifier Fail 2-of-N alarm – two or more rectifiers have at

 

Rect 2ofN Alm m+

[SYSTEM/SET-ALM]

 

least one alarm condition each.

 

Major

 

 

 

 

 

 

 

 

 

 

 

 

Hardware System Voltage

{2}

This alarm indicates there is a hardware failure in the system

 

Hw Sys V Alm

m+

[SYSTEM/SET-ALM]

 

voltage monitoring function.

 

Minor

 

 

 

 

 

 

 

 

 

 

 

Hardware Battery Current

{2}

This alarm indicates there is a hardware failure in the battery

 

Hw Batt C Alm m+

[SYSTEM/SET-ALM]

 

current monitoring function.

 

Minor

 

 

 

 

 

 

 

 

 

 

Hardware Battery Temperature {2}

This alarm indicates there is a hardware failure in the battery

 

Hw Batt T Alm m+

[SYSTEM/SET-ALM]

 

temperature monitoring function.

 

Minor

 

 

 

 

 

 

 

 

 

 

 

Hardware System Temperature {2}

This alarm indicates there is a hardware failure in the system

 

Hw Sys T Alm

m+

[SYSTEM/SET-ALM]

 

temperature monitoring function.

 

Minor

 

 

 

 

 

 

 

 

 

 

 

 

Hardware LVD1 {2}

 

This alarm indicates there is a conflict between the

 

Hw LVD1 Alm

m+

[SYSTEM/SET-ALM]

 

commanded and sensed positions of the LVD1.

 

Minor

 

 

 

 

 

 

 

 

 

 

 

 

Hardware LVD2 {2}

 

This alarm indicates there is a conflict between the

 

Hw LVD2 Alm

m+

[SYSTEM/SET-ALM]

 

commanded and sensed positions of the LVD2.

 

Minor

 

 

 

 

 

 

 

 

 

 

 

SYSTEM ALARMS DISPLAY

 

 

 

 

 

 

 

 

 

 

Alarms Item 1

 

Display of up to 16 active alarms (a typical alarm screen is

 

Alarm Item 1

+

[ALARMS]

 

shown).

 

Batt LV Alm On m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarms Item 16

 

Display of up to 16 active alarms (a typical alarm screen is

 

Alarm Item 16

+

[ALARMS]

 

shown).

 

 

 

 

 

 

 

 

 

SYSTEM DIAGNOSTICS

 

 

 

 

 

 

 

 

 

 

 

Store Configuration {1}

 

Setting this parameter to “Enable” will cause the current

 

Store Cfg

m+

[SYSTEM/DIAG]

 

rectifier configuration to be stored (the display toggles back

 

Disable

 

 

 

to “Disable” after entry).

 

 

 

 

 

 

 

 

 

 

 

 

 

Lamp Test {1}

 

Setting Lamp Test to “ON” will turn on the “MAJOR”,

 

Lamp Test

m+

[SYSTEM/DIAG]

 

“MINOR”, “NORMAL”, “MAJ”, and “MIN” LEDs on the

 

OFF

 

 

 

control unit front panel.

 

 

 

 

 

 

 

 

 

 

 

 

Test Relay Enable {1}

 

This parameter must be set to “Enable” to permit the eight

 

Test Relay En m+

[SYSTEM/DIAG]

 

output relays to be manually tested; otherwise, the state of the

Disable

 

 

 

relays will be per system conditions.

 

 

 

 

 

 

 

 

 

 

 

 

 

MX28B-1200/2400

41

Page 47
Image 47
APC MX28B-1200, MX28B-2400 manual Rect 1ofN Alm m+