MX28B-1200 PRODUCT MANUAL

Revision B

 

(Table 6.1 Parameter Locations, Descriptions, and Default Values)

 

 

 

 

PARAMETER

DESCRIPTION

DISPLAY SCREENS /

 

 

DEFAULT SETTINGS

Display Type

Type number for the control unit display.

Display Type

+

[SYSTEM/SETUP]

 

000255

 

 

 

 

 

 

 

 

Date/Time Setup

 

 

 

 

 

 

 

Date {1}

Internal system calendar date.

Date

m+

[SYSTEM/DATE]

 

DEC 16 1999

 

 

 

 

 

 

 

 

Time {1}

Internal system clock time (24-hour format).

Time

m+

[SYSTEM/DATE]

 

9:00:25

 

 

 

 

 

 

 

 

Alarm Threshold Setup

 

 

 

 

 

 

 

High Voltage Threshold {1}

System High voltage alarm threshold.

Sys HV Thr

m+

[SYSTEM/SET-ALM]

 

-58.00 V

 

 

 

 

 

 

Low Voltage Threshold {1}

System Low voltage alarm threshold.

Sys LV Thr

m+

[SYSTEM/SET-ALM]

 

-50.00 V

 

 

 

 

 

 

High Temperature Threshold {1}

Over temperature alarm threshold.

Sys HT Thr

m+

[SYSTEM/SET-ALM]

 

70.0 C

 

 

 

 

 

 

Low Temperature Threshold {1}

Under temperature alarm threshold.

Sys LT Thr

m+

[SYSTEM/SET-ALM]

 

0.0 C

 

 

 

 

 

 

System Status

 

 

 

 

 

 

 

System Voltage

System output voltage measured between the MX28B dc

Sys Voltage

+

[STATUS]

power plant -48V and return buses.

-54.00

V

 

 

 

 

 

 

System Current

The total system output current (calculated as the sum of the

Sys Current

+

[STATUS]

individual rectifier output currents).

145.8 A

 

 

 

 

 

 

System Temperature

System temperature measured within the control unit.

Sys Temp

+

[STATUS]

 

26.7

C

 

 

 

 

 

 

Battery Current

Battery current measured at the current shunt.

Batt Current

+

[STATUS]

 

-15.0 A

 

 

 

 

 

 

Battery Temperature

Battery temperature measured by the optional battery

Batt Temp

+

[STATUS]

temperature sensor probe.

25.2 C

 

 

 

 

 

 

System Alarms

 

 

 

 

 

 

 

System High Voltage {1}

System voltage is above the high voltage threshold.

Sys HV Alm

m+

[SYSTEM/SET-ALM]

 

Minor

 

 

 

 

 

 

 

 

System Low Voltage {1}

System voltage is below the low-voltage threshold.

Sys LV Alm

m+

[SYSTEM/SET-ALM]

 

Minor

 

 

 

 

 

 

 

 

System High Temperature {1}

The control unit temperature is above the high temperature

Sys HT Alm

m+

[SYSTEM/SET-ALM]

threshold.

Minor

 

 

 

 

 

 

 

 

40

MX28B-1200/2400

Page 46
Image 46