Electrical Requirements and Specifications

Procedures requiring a licensed electrician

A licensed electrician must connect utility power. The following procedures require a licensed electrician:

connection of utility conductors

installation of a 200- or 100-amp circuit breaker

connection to the main input switch

connection to a branch circuit

To connect utility power, see the utility connection instructions included with your documentation.

See also

Electrical requirements

 

200V Input

415V Input

 

 

 

Service distribution breaker 1,2

200A

100A

Conductors to Main Input switch1

3W + G

3W + G

Recommended wire sizing2,3

 

 

L1, L2, L3

60mm2

38mm2

G

14 mm2

8 mm2

 

 

 

1Provided by customer

2Consult national and local codes for requirements specific to your installation.

3CV or CVT cable