8 InfraStruXure Site Planning, Installation, Start-Up
Electrical Requirements and Specifications

Procedures requiring a licensed electrician

Electrical requirements

A licensed electrician must connect utility power. The following procedures
require a licensed electrician:
connection of utility conductors
installation of a 200- or 100-amp circuit breaker
connection to the main input switch
connection to a branch circuit
S
ee also
To connect utility power, see the utility connection instructions included with your
documentation.
200V Input 415V Input
Service distribution breaker 1,2 200A 100A
Conductors to Main Input switch13W + G 3W + G
Recommended wire sizing2,3
L1, L2, L3 60mm238mm2
G14mm
28mm
2
1 Provided by customer
2 Consult national and local codes for requirements specific to your installation.
3 CV or CVT cable