Electrical Requirements and Specifications
Procedures requiring a licensed electrician
A licensed electrician must connect utility power. The following procedures require a licensed electrician:
•connection of utility conductors
•installation of a 200- or 
•connection to the main input switch
•connection to a branch circuit
To connect utility power, see the utility connection instructions included with your documentation.
See also
Electrical requirements
  | 200V Input | 415V Input | 
  | 
  | 
  | 
Service distribution breaker 1,2  | 200A  | 100A  | 
Conductors to Main Input switch1  | 3W + G  | 3W + G  | 
Recommended wire sizing2,3  | 
  | 
  | 
L1, L2, L3  | 60mm2  | 38mm2  | 
G  | 14 mm2  | 8 mm2  | 
  | 
  | 
  | 
1Provided by customer
2Consult national and local codes for requirements specific to your installation.
3CV or CVT cable