Connect User Contact Inputs and Output Relays to the User Connection Plate

Overview

Make contact closure connections (NO or NC) at the user connection plate to monitor dry contacts. You can make eight connections—four contact inputs and four output relays.

The figure at the right shows the location of the user connection plate on the roof of the PDU enclosure.

You can make connections from inside the enclosure, or you can remove the user connection plate and make your connections.

Remove the plate using a Phillips or standard screw driver to loosen the two captive screws. Use the knockout in the plate to route cables to and from the user connections on the plate. If you remove the plate, make sure that you do not disturb the existing connections.

Output relay specifications

USER INTERFACE

© 2001 APC

MADE IN USA

1

2

3

4

 

 

Contact Outputs

 

 

Contact Inputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATS 0 ATS 1 ATS 2

ATSEN

+ EPO 24V EPO AC/DC Contact

Nominal switching capacity:

1A at 30VDC

Maximum switching power:

30W

Maximum switching voltage:

60VDC

Maximum switching current:

2ADC

Maximum carrying current:

2ADC

Surge ratings:

2kV per Bellcore TA-NWT-001089

 

1.5kV per FCC part 68

InfraStruXure Site Planning, Installation, Start-Up