APC Switched Rack Power Distribution Unit (PDU) Watchdog Features, Resetting the network timer

Models: Switched Rack Power Distribution Unit (PDU)

1 93
Download 93 pages 3.89 Kb
Page 16
Image 16

USER’S GUIDE switched rack pdu

®

Watchdog Features

Overview

To detect internal problems and recover from unanticipated inputs, the PDU uses internal, system-wide watchdog mechanisms. When it restarts itself to recover from an internal problem, a System: Warmstart event is recorded in the Event Log.

Network interface watchdog mechanism

The PDU implements internal watchdog mechanisms to protect itself from becoming inaccessible over the network. For example, if the PDU does not receive any network traffic for 9.5 minutes (either direct traffic, such as SNMP, or broadcast traffic, such as an Address Resolution Protocol [ARP] request), it assumes that there is a problem with its network interface and restarts itself.

Resetting the network timer

To ensure that the PDU does not restart if the network is quiet for 9.5 minutes, the PDU attempts to contact the Default Gateway every 4.5 minutes. If the gateway is present, it responds to the PDU, and that response restarts the 9.5-minute timer. If your application does not require or have a gateway, specify the IP address of a computer that is running on the network most of the time and is on the same subnet. The network traffic of that computer will restart the 9.5-minute timer frequently enough to prevent the PDU from restarting.

12

Page 16
Image 16
APC Switched Rack Power Distribution Unit (PDU) manual Watchdog Features, Network interface watchdog mechanism