CHAPTER 5: SPECIFICATIONS
| Output Specifications |
|
|
Nominal Output Voltage | 200, 208, 220, 230, 240 Vac; 50 or 60 Hz, 1 phase, 3 wire |
|
|
Output Power kVA | 4 – 16 kVA |
|
|
Output Power kW | 2.8 – 11.2 kW |
|
|
Load Power Factor | 0 – 1 |
|
|
Output Frequency | 60 or 50 Hz nominal |
|
|
Output Voltage Regulation | < ± 3% for no load to full load, min ac input to max ac, min dc to max dc, |
Steady State | linear or |
|
|
Output Voltage Regulation | < ± 5% for 100% load application or removal, linear or |
Transient/Dynamic |
|
|
|
Recovery Time | < 10 milliseconds (i.e. half cycle to steady state) |
|
|
Total Harmonic Distortion | < 2% for linear loads; < 5% for |
|
|
Load Crest Factor Supported | < 5% for 100% |
|
|
Overload Capacity | 130% for 10 minutes. With N+1 |
|
|
Efficiency | Approximately 90% @ full |
|
|
| Physical Specifications |
|
|
Audible Noise | < 62 dBA |
|
|
Dimensions (H x W x D) | 26.1 in x 18.9 in x 27.8 in (with bezel) |
| (66.3 cm x 48.0 cm x 70.6 cm) |
|
|
Weight – Fully Loaded | Approximately 557 lb (133.6 kg) |
|
|
Heat Dissipation (Full Load) | 4246 BTUs typical – Batteries charged |
| 9664 BTUs typical – Batteries charging |
|
|
| Compliance Specifications |
|
|
EN 60950, EN | |
| VDE 0558 and VDE 0805 |
|
|
UL Listing | UL 1778 |
|
|
CSA Certification | CSA 107.1 |
|
|