CHAPTER 2: BASICS
9
Product Overview

Front View Component Identification

Figure 1: UPS – Front View
PowerView and Bezels Removed
Figure 2: UPS – Front and Side View
Power Module(s) : Each module can provide up
to 4 kVA/2.8 KW power. The UPS frame can support
up to four power modules.
Main Intelligence Module : The Main Intelligence
Module (MIM) performs all monitoring, control, and
communication functions for the UPS.
Redundant Intelligence Module : The
Redundant Intelligence Module (RIM) provides
backup in the event of a MIM failure.
Battery Module(s) : Each battery module
provides backup energy storage. The UPS frame
can support up to four battery modules.
Input Circuit Breaker : The input circuit breaker
protects the UPS and load equipment from extreme
overloads.
Maintenance Bypass Switch : Manual control of
the bypass function. When the maintenance bypass
switch is in the “ON” position, power is delivered
directly from the branch circuit (mains) to the load
equipment.
Rail Cleats : Two cleats (one on each side)
engage with the rack mounting rails to secure the
UPS in the rack.
Mounting Flanges : Two mounting flanges are
used to secure the UPS to the rack.
PowerView : The user interface can be
programmed to provide full control, monitoring, and
configuration for the UPS.
Front Bezels : Blank faceplates cover the power
modules, battery modules, and unoccupied bays in
the front of the UPS.