CHAPTER 3: SITE PREPARATION
14
Shipping & Receiving
The UPS and modular components are shipped on one or more pallets, depending on the configuration. The frame is
installed first and then modular components are installed within the frame.
Weights and
Measurements
Length
Inches (cm)
Width
Inches (cm)
Height
Inches (cm)
Weight
lbs (kg)
Unpackaged
Chassis* 27.8 (70.6) 18.9 (48.0) 26.1 (66.3) 185.0 (84.1)
Power module 23.4 (59.4) 10.0 (25.4) 5.2 (13.2) 29.0 (13.2)
Battery module 23.5 (59.7) 6.6 (16.8) 5.2 (13.2) 64.0 (29.1)
Intelligence modules 19.6 (49.8) 6.6 (16.8) 1.6 (4.1) 5.0 (2.3)
Packaged
Chassis** 36.0 (91.4) 30.0 (76.2) 37.4 (95.0) 264.0 (120.0)
Power module 30.8 (78.2) 12.3 (31.2) 17.0 (43.2) 35.0 (15.9)
Battery module 30.8 (78.2) 12.3 (31.2) 17.0 (43.2) 70.0 (31.8)
Intelligence modules 22.8 (57.9) 12.5 (31.8) 7.3 (18.5) 7.0 (3.2)
* Overall length including bezel
** Includes rail and accessory bezel kit
Short-Term Battery Module Storage Requirements
Do not install battery modules until you are ready to power up the UPS. Batteries can be
permanently damaged if loaded prematurely.
Store the battery module(s) at a cool ambient temperature of < 25 °C.
Storage of batteries longer than six months without recharging may result in permanent
damage.