| In calculating the lengths of the pipes, the | ||||||
TWIN PIPE | maximum length “L” must also take into | ||||||
SYSTEMS | consideration | the | values | for | the | ||
exhaust/air intake end terminals, as well | |||||||
| |||||||
| as 90° elbows for coaxial systems. |
| |||||
| The C52 types must comply with the | ||||||
| following requirements: |
|
| ||||
| 1 - | The exhaust/ air intake pipes must | |||||
|
| have the same diameter of ø | 80 mm. | ||||
| 2 - | If elbows are to be inserted into the | |||||
|
| air intake and/or exhaust system, the | |||||
|
| calculation of the overall length must | |||||
|
| take into consideration the values for | |||||
|
| each elbow, see the FL U E | PI P E | ||||
|
| ACCESSORIES MANUAL. |
|
| |||
| 3 - The exhaust pipe must protrude by at | ||||||
|
| least 0.5 m above the top of the roof | |||||
|
| in the event that it is located on the | |||||
|
| opposite side to the side with the air | |||||
|
| intake (this condition is not obligatory | |||||
|
| when the air intake and exhaust are | |||||
|
| located on the same side of the | |||||
|
| building). |
|
|
|
| |
FIG. 2.11 | FU007A |
|
|
|
|
| |
|
|
|
|
|
|
2.10ROOM THERMOSTAT CONNECTION
To connect a room thermostat, it is necessary to:
1. - Open the control panel as indicated in section 3.3.
2.- Remove the link “A” from the terminal block on the reverse of the control panel.
3.- Insert the thermostat cable through the cable grommet and fasten it by means of the
4.- Then connect the thermostat wires to the terminal block.
5.- If a remote time clock is to be fitted, disconnect the integral time clock from the P.C.B.
6.- Using a
7.- If using an external time clock and room thermostat, these must be connected in series as points
Note: Only a
An
A
Fo016A
12
Fo017A