B&B Electronics HVD100A3 manual Broadcast Message, Byte, Function, Number, Value

Models: HVD100A3

1 31
Download 31 pages 45.58 Kb
Page 21
Image 21
Broadcast Message

Broadcast Message

The HDV100A3 supports one broadcast message. Once configured by the host application, this message will be sent repeatedly by the HDV100A3 at a programmed time interval. This feature is useful to provide a “heartbeat” function to the J1708 bus with no overhead to the host application’s software. Sending 0 in the time value stops the broadcast message from being sent.

To start a broadcast message the time interval, message slot, priority, number of data bytes, and the data must be sent to the HDV100A3. Once sent, the HDV100A3 will send the message out on the bus at the specified interval. Existing bus traffic or any bus messages sent to the HDV100A3 from the host application take priority over a pending broadcast message.

Once a broadcast message is started the “Stop Broadcast 07” message must be sent before any changes to the broadcast message can be made. Changing from one time value (17) to another (37) without stopping the broadcast will cause the HDV100A3 to act erratically.

Byte

Byte

Function

Number

Value

 

 

 

 

1

01

Start of frame

2

04

Control bytes

3

01

ID byte 1 = J1708 message

4

X7

Set broadcast 7 = On X = Time interval (see chart)

5

0X

Message slot number (01 only active at this time)

6

PP

Priority (see chart below)

7

YY

Data bytes

 

DATA

From 4 to 21 bytes

 

CS

Checksum

HDV100A3 Command & Response Manual-1306cr

17

B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350

PH (815) 433-5100 -- FAX (815) 433-5104

Page 21
Image 21