5.3.1.1Error relay connections

The double-pole relay on the opto-isolator card is controlled directly by the Error Out signal (section 4.4.3), as shown in Figure 29.

NextMove ES

MintMT

GLOBALERROROUTPUT

or

DRIVEENABLEOUTPUT

Control circuitry

Error Out

+5V

Backplane

 

 

 

‘X8’

 

Relay

REL COM

 

7

96

 

 

pin

 

 

connector

 

 

 

9

REL NO

 

8

REL NC

Figure 29 - Relay connections

The error output can be controlled by the RELAY keyword, and can be configured as the global error output by setting GLOBALERROROUTPUT to 1000 (_RELAY0). See the Mint MT help file.

While there is no error, the relay is energized, and REL COM is connected to REL NO. When an error occurs, the relay is de-energized, and REL COM is connected to REL NC.

CAUTION: It is important that the NextMove ES jumper settings are correct to allow it to control the backplane relay. JP4 and JP5 must be fitted. Jumper JP3 must be removed. See section 4.4.3 for jumper locations.