3.2.11 Connecting Power and SDI, Terminals 1, 3, 5, 6, and 7

D9210B

Installation

3.2.11 Connecting Power and SDI, Terminals 1, 3, 5, 6, and 7

Do not connect 24 VDC or non-isolated [from the strike] 12/24 VAC of the D9210B.

Reference Figure 5 for the following connections.

Terminal 1, Pwr +12 VDC IN. The red wire provides power to the D9210B, 12 VDC readers and buzzers. Terminal 3, LCKCOM. For 12/24 VDC strikes provide the input power here from the power supply.

Terminal 5, Common. The black conductor provides electrical common between the D9210B and the power source.

Always ensure a common exist from the D9210B to the panel so the power supply and panel have the same ground reference. Use any common terminal on the D9210B, 5, 9 or 12 for connections.

Terminal 6, SDI A PANEL DATA (INPUT). The yellow conductor from the panel connected to this terminal. This is where data from the panel is received by the D9210B.

Terminal 7, SDI B PANEL DATA IN (RETURN). The green conductor from the panel is connected to this terminal. This is where the data from the D9210B is returned back to the panel.

 

 

12 VDC AUX

 

 

 

Power Supply

 

 

 

UL Listed for Fire

 

 

 

DC OUTPUT

 

 

 

(red)

 

 

 

D9210B

 

 

 

(black)

 

 

 

1

 

 

 

PWR +

 

 

 

2

 

Security

 

LCKN/C

Security

 

3

Panel

 

LCKCOM

Panel

 

4

 

 

 

 

 

LCKN/O

 

SDI

 

5

SDI

 

COM

PWR

 

6

PWR

SDI

(white / yellow)

 

SDIA

SDI

A

 

 

 

 

A

SDI

(green)

7

SDI

B

SDIB

 

B

SDI

(black)

8

SDI

COM

T +

COM

 

 

 

 

 

9

 

 

 

ZNCOM

 

 

 

10

 

 

 

ZN +

 

(white / yellow)

Figure 5: Power Supply and SDI Connections (green)

(black)

24VDC

AUX Power

Supply

(Optional)

DC OUTPUT

(red)

(black)

D9210B

1

PWR +

2

LCKN/C

3

LCKCOM

4

LCKN/O

5

COM

6

SDIA

7

SDIB

8

T +

9

ZNCOM

10

ZN +

Note: In installations where powering the D9210B with the security panel is impractical, a 12 VDC power supply can be substituted.

Figure 5: Power Supply and SDI Connections

It is very important to include your strike current. Bosch Security Systems recommends you use an auxiliary power supply to isolate door controls and ensure the integrity of the system.

Technical

Tip

3.2.12 Programming and Activating the D9210B

Description. The D9210B needs to be assigned to an area before it will communicate properly with the panel. In addition, the dipswitch settings and the power need to be connected.

The dipswitch settings in Table 8: D9210B Dipswitch Settings, p.19 determine the address of the D9210B. At the top of the

ACCESS Program Record Sheet (P/N:33208), the address number (noted next to the dipswitch setting in Figure 4: D9210B DIP Switch

(Factory Settings), p.19) will determine which parameters for the door controller are sent.

D9210B Operation and Installation Guide

32206G

Page 20

© 2002 Bosch Security Systems

Page 20
Image 20
Bosch Appliances D9210B manual Connecting Power and SDI, Terminals 1, 3, 5, 6, and, Power Supply and SDI Connections