SMC Networks EX500-GEN1 Sensor wiring, Correspondence between input number and input block

Models: EX500-GEN1

1 23
Download 23 pages 14.41 Kb
Page 17
Image 17

Wiring

Branch wiring

For wiring method, refer to subsection "Wiring" ( page 15 ) of section "EX500" in this manual. To input devices such as sensor, the power is supplied through the branch wiring ( branch cable with M12 connector ). Therefore, there is no need to supply the power to them individually.

Sensor wiring

Sensor connector "1"

Connect sensors to the sensor

Sensor connector "0"

connectors of input block.

 

Pin layout of sensor connector

M8 connector ( 3-pin socket )

 

M12 connector ( 4-pin socket )

 

Power supply

 

 

Power supply

 

 

( 24VDC )

1

 

( 24VDC )

1

2

Power supply ( 0V )

 

 

( Input ) ( Note )

 

 

Input

4

3

Power supply ( 0V )

4

3

 

Input

 

 

 

 

 

Note : Internal wiring of M12 input block and key position for mounting sensor connector

Correspondence between input number and input block

Input block up to 8 can be connected ( 16 points ).

Input numbers are 0 to 15 from Input unit side.

Input unit 0

2

4

6

8

10

12

 

14

0

0

0

0

0

 

0

0

0

1

1

1

1

1

 

1

1

1

1

3

5

7

9

11

13

 

15

Display

Power LED

Indicator LED

No. 2 pins of M12 input block connectors are wired to each other’s sensor signal input pins ( No. 4 pins ) internally.

This wiring enables direct input of signals from two points combined into one cable through concentric connector etc.

When connecting sensors, confirm the specification of output signal carefully. Otherwise malfunction can result.

The key position for mounting sensor connector is as shown to the right. Consider this key position when selecting sensor.

Input "0" ( n ) side

Input "1" ( n+1 ) side

4

 

 

2

0

 

key

1

 

 

 

3

1

1

3

2

key

 

4

 

 

Input "1" ( n+1 )

 

 

 

Input "0" ( n )

 

 

 

M12 Block

Display

Description

Power LED

Lights on : Power for input and controlling GW is supplied.

 

Blinks : Under short circuit protection ( abnormal status ).

 

As the short circuit protective function is operating, the power

 

is not supplied.

 

To cancel blinking, turn off and return the power to GW unit.

 

Lights off : Power for input and controlling GW is not supplied.

NOTE

Mount a waterproof cap on each unused connector of Input unit. The proper use of waterproof cap can achieve IP65 Enclosure. The waterproof caps are delivered together with each input block as accessories.

( Tightening torque : 0.05Nm for M8 and 0.1Nm for M12 )

Indicator

Lights on : Sensor signal input ON ( logical "1" )

LED

Lights off : Sensor signal input OFF ( logical "0" )

30

31

Page 17
Image 17
SMC Networks EX500-GEN1 Sensor wiring, Correspondence between input number and input block, Connect sensors to the sensor