SMC Networks EX500-GEN1 Troubleshooting, Overall system, EtherNet/IP compatible communication

Models: EX500-GEN1

1 23
Download 23 pages 14.41 Kb
Page 23
Image 23

Troubleshooting

Overall system

No.

Item

Solution/Corrective action

1

Solenoid valve

Check the power for solenoid valves/output ( 24VDC )

 

doesn't work

is supplied.

 

 

Check the connection of the branch cable with M12

 

 

connector to SI unit.

 

 

Check Power LED and Communication LEDs of SI

 

 

unit light on.

 

 

 

2

Solenoid valve doesn't

Check the wiring specification for manifold block

 

work as programmed

assembly and modify the program.

 

 

 

3

Power LED of

Short circuit of input sensor due to failure etc. is

 

Input unit is blinking

possibly caused. Check the sensor.

 

 

A current larger than specified value is flowing

 

 

through the power line for input and controlling

 

 

GW/SI. Check the power supply section.

 

 

 

4

No signal is input even

Check the power for input and controlling GW/SI

 

though connected with

( 24VDC ) is supplied.

 

sensor(s)

Check indicator LED of each block lights on.

 

 

 

5

COM A - D LED

Check Input unit is connected to the branch of unlit

 

doesn't light on

COM port, and the branch cable with M12 connector

 

 

is connected to the Input unit.

 

 

When connecting no Input unit, connect a terminal

 

 

plug.

 

 

 

EtherNet/IP compatible communication

No.

Item

Solution/Corrective action

1

MS LED status

The effect of noise is possible. Check

 

Normal status : Lit in green

the installation conditions. If the trouble

 

Fatal failure : Lit in red

cannot be solved even if the installation

 

 

conditions are checked, contact our

 

 

sales branch.

 

 

 

2

NS LED status

Check the signal line from PLC is

 

Offline/Power is OFF : Unlit

connected.

 

Online/Communication is not established :

Check the wiring and pin Nos.

 

Blinking in green

Check the data rate and address

 

Online/Communication is established :

setting.

 

Lit in green

 

 

Minor communication error occurred :

 

 

Blinking in red

 

 

Fatal communication error occurred :

 

 

Lit in red

 

 

 

 

3

PWR LED is unlit

Check the power for solenoid

 

 

valves/output (24VDC) is supplied.

 

 

Check the power supply voltage for

 

 

solenoid valves/output doesn't drop

 

 

under 20V.

 

 

 

42

43

Page 23
Image 23