10 en Install the Bases

F220 Series Detectors with F220-B6RS Bases

 

 

3.2Wire the Bases

CAUTION! When wiring bases, all terminal screws

!including those not wired must be tightened to prevent loose screw heads from making intermitent electrical

contact with the detector head.

3.2.1Terminal Connections

WARNING! Do not twist or loop the wires around the terminals. In and out wires for terminal connection must

!be cut, stripped, and inserted as individual ends.

NOTE! Bring the positive (+) wires in on terminal b2 and

i out from terminal b1. Use a consistent pattern, inputting on b2 and outputting from b1. The negative (-) wires input and output from the same terminal (a1/a2).

3.2.2EOL Resistors

Use the EOL resistors supplied or specified by the control panel manufacturer. This applies to all loop terminations including the D275 Module and the F220-B6E Power Supervision Base.

3.2.3Loop Wiring Specifications

In a four-wire system, the maximum loop length and number of bases that can be placed on a loop depend on the voltage drop on the power circuit. Use standard voltage drop calculations to ensure that the last detector on the loop meets the minimum voltage requirement of at least 16 V.