Bosch Appliances F220-B6RS installation manual Position 1 and 2 on

Models: F220-B6RS F220

1 28
Download 28 pages 37.61 Kb
Page 15
Image 15
Position 1 and 2 on;

F220 Series Detectors with F220-B6RS BasesInstall the Bases en 15

Position 1 and 2 on;

Sounder output configured for steady

3 and 4 either both on

signal (continuous tone)

or both off.

 

 

 

 

 

 

 

 

 

 

O

N

D

 

I P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

2

 

 

3

 

 

 

4

 

 

Position 1, 2, and 3 on;

Sounder output configured for

4 off.

 

 

 

 

 

 

 

 

 

 

 

 

Temporal Code 3 signal

 

O

N

D

 

I P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

2

 

 

3

 

 

 

4

 

 

Position 1, 2, and 4 on;

Sounder output configured for March

3 off.

 

 

 

 

 

 

 

 

 

 

 

 

Time signal

 

O

N

D

I P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

Table 3.2 Local Configuration DIP Switch Settings

NOTE! Up to five interconnected units activate per circuit. If more than five units activate, only individual

i detectors are guaranteed to activate the correct output pattern. Additional interconnected units cannot activate the correct output pattern.

Bosch Security Systems, Inc.

Installation Manual

F.01U.029.847 -01 2007.02

Page 15
Image 15
Bosch Appliances F220-B6RS installation manual Position 1 and 2 on