F220 Series Detectors with F220-B6RS Bases

Install the Bases en 19

 

 

The alarm loop relay (Form A, Terminals 1 and 2) and the power supervision relay (Terminal 3 and 4) are rated for 0.5 A at 120 VAC/DC for resistive loads.

!

CAUTION! Do not connect relays to inductive or

capacitive loads. Use with resistive loads only.

 

3.5.2 Wire D275 Power Supervision Module

When a D275 Module is used with 24 VDC systems, connect the yellow wire to the output terminal (b1 or b2). The red wire remains unconnected (refer to Figure 3.5 on page 19).

 

1

 

3

2

D275

2

 

 

 

 

4

+12 VDC

7

5

+24 VDC

 

6

Common (-)

1.

EOL resistor (refer to the

 

to Terminal 1 on the last

 

control panel’s

 

base on the loop.

 

installation instructions

4.

Red wire is not used.

 

for specifications).

5.

Yellow wire to Terminal b1

2.

The positive (+) and

 

on last base on loop for

 

negative (-) IDC wires

 

24 VDC systems.

 

(blue) from the D275.

6.

Black wire (common) to

3.

Connect the positive (+)

 

Terminal a1/a2 on last

 

IDC wire through the EOL

 

base on loop.

 

resistor to Terminal 2 and

7.

Power loop

 

the negative (-) IDC wire

 

 

 

 

 

 

Fig. 3.5 Wiring a D275 Power Supervision Module as a Loop Terminator

Bosch Security Systems, Inc.

Installation Manual

F.01U.029.847 -01 2007.02

Page 19