3.4.2Local Configurations

F220 Series Detectors with F220-B6RS Bases

Install the Bases en 13

 

 

3.4.2Local Configurations

In these configurations, the sounders are controlled and powered from the control panel’s power circuit (refer to Figure 3.2, Items 1 and 2 on page 14). The initiating device circuit (IDC) wires connect to Terminals 1 and 2 (refer to Figure 3.2, Items 3 and 4 on page 14). The DIP Switches are set for one of the following patterns: Temporal (Code 3), March Time, or Continuous Tone (refer to Table 3.2 on page 15).

Local Configuration: Each sounder is individually set and activated (refer to Table 3.2 on page 15).

Interconnection Configuration: Up to five detectors can be interconnected by a common wire (refer to Figure 3.2, Item 4 on page 14, Table 3.2 on page 15, and Figure 3.3 on page 17). All sounders within the group activate together. Set all units for the same output pattern (Temporal Code 3, March Time, or Continuous Tone). All interconnected detectors are synchronized with and sound the pattern of the originating detector.