Bryant 551A 15, H. Ventilation Air Minimum Position Set Up, Ix. — Install All Accessories

Models: 551A

1 36
Download 36 pages 40.32 Kb
Page 15
Image 15
H. Ventilation Air (Minimum Position Set Up)

H. Ventilation Air (Minimum Position Set Up)

If ventilation air is not required, skip this section. If ventila- tion air is required, perform the following:

1.The indoor fan must be on to set the ventilation air. Either put the thermostat in the continuous fan mode or jumper the R and G terminals at the rooftop unit connection board.

2.Locate the minimum position (MIN POS) potentiome- ter. Turn the potentiometer full CCW to fully close the outdoor air dampers. Turn the potentiometer gradually clockwise (CW) to the desired position. See Fig. 16.

3.Replace the filter access panel. See Fig. 18. Ensure the filter access panel is securely engaged.

4.Calculate the minimum airflow across the EconoMi$er.

a.Calculate % of outside air using the following formula.

% Outdoor air through EconoMi$er

% Outdoor

=

Mixture Temp – Return Air Temp

air

Outdoor Temp – Return Air Temp

 

b.Multiply total CFM by percentage outdoor air, this gives outdoor air volume in CFM.

IX. STEP 9 — INSTALL ALL ACCESSORIES WARNING: Personal Injury Hazard. Avoid possible injury by keeping fingers away from damper blades.

IX. STEP 9 — INSTALL ALL ACCESSORIES

After all the factory-installed options have been adjusted, install all field-installed accessories. Refer to the accessory installation instructions included with each accessory.

A. Motormaster® I Control Installation (551A155 and 180 Only)

Install Field-Fabricated Wind Baffles

Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 25 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should be 1/4-in. diameter and 5/8-in. long. Drill required screw holes for mounting baffles.

Fig. 24 — Typical EconoMi$er Sensor Wiring CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.

—15—Manual background Unoccupied Control (Part number on the control

must be AD-DME1701-1 or AD-DME1711-1.)

Outdoor Air Enthalpy

 

 

 

CROUTENT001A00

 

Unoccupied

 

 

 

Contact

470 ohm

 

 

 

5 watt

 

T

Violet

Resistor

C

 

O

 

 

O

U

 

 

M

T T

 

 

 

PW

 

 

 

 

Tan

OAT

 

Violet

COM

 

W hite

 

 

24 VAC must be present on BI for the system to be Manual backgroundManual background unoccupied.

OAH

 

Red

 

+15V

 

 

 

 

 

 

 

 

 

Tan

 

 

 

 

 

 

 

 

 

RAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Violet

COM

 

 

 

 

 

 

 

 

 

 

RAH

 

 

 

 

 

 

 

 

W hite

 

 

Red

+15V

 

 

 

 

 

 

 

 

 

 

 

 

 

CO 2(+)

 

 

 

 

 

 

 

 

 

 

CO 2

 

 

 

 

 

COM

 

 

 

 

 

DAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REM

 

POT

 

 

 

 

COM

 

 

 

 

LED

 

 

 

 

 

 

 

 

COM

 

 

 

 

Violet

C TO

O U Manual backgroundManual background

M T T

PW

Remote

Minimum Position

1k ohm Potentiometer

20 mA LED

Remote

LED

Field-supplied W iring

Return Air Enthalpy

CRRETENT001A00

CO2 Sensors:

CRCDXSEN004A00

 

 

2 to 10 VDC at

 

 

0 to 2000 ppm

NOT 2 USED

VAC24 VA20

Line

 

 

 

 

Voltage

1

 

 

-

 

 

W iring Included

Fig. 24 — Typical EconoMi$er Sensor Wiring

15

Page 15
Image 15
Bryant 551A operation manual 15, H. Ventilation Air Minimum Position Set Up, Ix. — Install All Accessories