Table 14 — Perfect Humidity™ Dehumidification

Package Static Pressure Drop (in. wg)

UNIT SIZE

UNIT NOMINAL

CFM PER TON

551A

TONS

300

400

500

155

12

.026

.045

.071

180

15

.040

.071

.111

240

20

.071

.126

.197

Table 15 — Fan RPM at Motor Pulley Settings*

551A

0

0.5

1

11/

2

2

21/

2

3

31/

2

4

41/

5

51/

2

6

 

 

 

 

 

 

 

 

 

 

2

 

 

 

155†

††

††

††

††

1064

1035

1006

978

949

920

891

863

834

155**

††

††

††

††

1426

1393

1360

1327

1294

1261

1227

1194

1161

180†

††

††

††

††

1021

1002

984

965

947

928

910

891

873

180**

††

††

††

††

1200

1178

1156

1134

1112

1091

1069

1047

1025

240†

††

††

††

††

1151

1132

1114

1095

1077

1058

1040

1021

1002

240**

††

††

††

††

1369

1347

1325

1303

1281

1259

1237

1215

1193

*Approximate fan rpm shown.

†Indicates standard drive package. **Indicates alternate drive package.

††Due to belt and pulley style, pulley cannot be set to this number of turns open.

Table 16 — Evaporator Fan Motor Specifications

UNIT

NOMINAL

VOLTAGE

MAX

EFF.

MAX

MAX

MAX

551A

HP

WATTS

%

BHP

BkW

AMPS

 

155

2.9

208

2700

85.8

3.13

2.34

9.46

(Standard

2.9

230

2700

85.8

3.13

2.34

8.6

Motor)

2.9

460

2700

85.8

3.13

2.34

4.3

155

3.7

208

3775

85.8

4.38

3.27

10.5

(Optional

3.7

230

3775

85.8

4.38

3.27

10.5

Motor)

3.7

460

3775

85.8

4.38

3.27

4.8

180

5

208

5180

87.5

6.13

4.57

15.8

5

230

5180

87.5

6.13

4.57

15.8

 

5

460

5180

87.5

6.13

4.57

7.9

240

7.5

208

7915

88.5

9.47

7.06

22

7.5

230

8640

88.5

10.33

7.71

22

 

7.5

460

8640

88.5

10.33

7.71

13

LEGEND

BHP — Brake Horsepower

25

Page 25
Image 25
Bryant 551A operation manual Fan RPM at Motor Pulley Settings, Evaporator Fan Motor Specifications