Bryant operation manual Base Unit Dimensions, 551A240

Models: 551A

1 36
Download 36 pages 40.32 Kb
Page 5
Image 5
Fig. 5 — Base Unit Dimensions, 551A240

5

UNIT

STD UNIT

ECONOMI$ER

CORNER

CORNER

CORNER

CORNER

DIM A

DIM B

DIM C

WEIGHT

WEIGHT

 

A

 

B

 

C

 

D

551A

 

 

 

 

 

 

 

 

 

 

Lb

Kg

Lb

Kg

Lb

 

Kg

Lb

 

Kg

Lb

 

Kg

Lb

 

Kg

ft-in.

mm

ft-in.

mm

ft-in.

mm

 

 

 

 

 

240

1750

794

80

36.3

420

 

191

395

 

179

448

 

203

486

 

221

3-3

988

3-5

1054

1-8

508

NOTES:

1.Refer to print for roof curb accessory dimensions.

2.Dimensions in ( ) are in millimeters.

3.Manual background Center of Gravity.

4.Manual background Direction of airflow.

5.Ductwork to be attached to accessory roof curb only.

6.Minimum clearance:

Rear: 7-0(2134) for coil removal. This dimension can be reduced to 4-0(1219) if conditions permit coil removal from the top.

Left side: 4-0(1219) for proper condenser coil airflow.

Front: 4-0(1219) for control box access.

Right side: 4-0(1219) for proper operation of damper and power exhaust if so equipped.

Top: 6-0(1829) to assure proper condenser fan operation.

Local codes or jurisdiction may prevail.

7.With the exception of clearance for the condenser coil and the damper/ power exhaust as stated in Note #6, a removable fence or barricade requires no clearance.

8.Dimensions are from outside of corner post. Allow 0-5/16(8) on each side for top cover drip edge.

9.See drawing 50TJ500352 for service option details.

10.A 90 degree elbow must be installed on the supply ductwork below the unit discharge for units equipped with electric heaters.

Fig. 5 — Base Unit Dimensions, 551A240

Page 5
Image 5
Bryant operation manual Base Unit Dimensions, 551A240