Table 15 — Fan Performance — 580F210275 (Low Heat Units)*

AIRFLOW

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

 

1.2

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5,500

755

2.27

1908

831

2.58

2171

901

2.91

2443

968

3.24

2723

1031

3.58

3009

1091

3.93

3302

6,000

810

2.72

2287

881

3.04

2556

947

3.37

2833

1010

3.71

3116

1070

4.05

3406

1127

4.40

3702

6,500

866

3.22

2710

932

3.55

2985

994

3.88

3266

1054

4.23

3554

1111

4.57

3847

1166

4.93

4146

7,000

923

3.78

3177

985

4.11

3458

1044

4.45

3744

1100

4.80

4036

1155

5.15

4333

1207

5.51

4635

7,500

980

4.39

3690

1038

4.73

3976

1094

5.07

4267

1148

5.43

4564

1200

5.78

4864

1250

6.15

5170

8,000

1038

5.06

4251

1093

5.40

4542

1146

5.75

4838

1197

6.11

5138

1246

6.47

5443

1294

6.84

5752

8,500

1096

5.78

4859

1148

6.13

5156

1198

6.49

5456

1247

6.85

5761

1294

7.22

6070

1340

7.59

6382

9,000

1154

6.56

5517

1204

6.92

5818

1251

7.28

6123

1298

7.65

6432

1343

8.02

6745

1388

8.40

7062

9,500

1213

7.40

6224

1260

7.77

6531

1306

8.13

6840

1350

8.51

7154

1394

8.88

7471

1436

9.26

7791

10,000

1272

8.30

6983

1317

8.67

7294

1360

9.05

7608

1403

9.43

7926

1445

9.81

8247

1486

10.19

8570

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

1.4

 

 

1.6

 

 

1.8

 

 

1.9

 

 

2.0

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

 

5,500

1149

4.28

3602

1204

4.65

3907

1258

5.02

4217

1284

5.20

4375

1309

5.39

4533

 

 

 

6,000

1183

4.76

4003

1236

5.13

4310

1288

5.50

4622

1313

5.68

4780

1337

5.87

4939

 

 

 

6,500

1219

5.29

4450

1270

5.66

4759

1320

6.03

5073

1344

6.22

5232

1368

6.41

5391

 

 

 

7,000

1258

5.88

4942

1307

6.25

5253

1355

6.62

5569

1378

6.81

5729

1402

7.00

5890

 

 

 

7,500

1299

6.52

5480

1346

6.89

5794

1392

7.27

6113

1415

7.46

6273

1437

7.65

6435

 

 

 

8,000

1341

7.21

6065

1387

7.59

6383

1392

7.97

6704

1453

8.16

6866

1475

8.36

7028

 

 

 

8,500

1385

7.97

6699

1429

8.35

7019

1472

8.73

7343

1493

8.93

7506

1514

9.12

7670

 

 

 

9,000

1431

8.78

7382

1473

9.15

7705

1515

9.55

8032

1535

9.75

8196

 

 

 

9,500

1478

9.65

8114

1519

10.04

8441

 

 

 

10,000

 

 

 

LEGEND

Bhp — Brake Horsepower

Watts — Input Watts to Motor

*Standard low-medium static drive range is 910 to 1095 rpm. Alternate high-static drive range is 1069 to 1287. Other rpms require a field- supplied drive.

Refer to page 32 for general Fan Performance Data notes.

NOTE: Maximum continuous bhp is 5.90. The maximum continuous watts is 5180. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Table 24 for more information.

Table 16 — Fan Performance — 580F210360 (High Heat Units)*

AIRFLOW

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

 

1.2

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5,500

795

2.43

2043

866

2.74

2306

934

3.07

2578

998

3.40

2856

1059

3.74

3142

1117

4.08

3434

6,000

854

2.92

2452

921

3.24

2722

984

3.57

3998

1044

3.90

3281

1102

4.25

3570

1158

4.60

3865

6,500

914

3.46

2909

977

3.79

3184

1036

4.12

3465

1093

4.46

3752

1148

4.81

4045

1201

5.16

4343

7,000

975

4.06

3414

1034

4.39

3695

1090

4.73

3981

1144

5.08

4272

1196

5.43

4569

1246

5.79

4870

7,500

1037

4.72

3969

1092

5.06

4255

1145

5.41

4546

1196

5.76

4842

1256

6.12

5142

1294

6.48

5447

8,000

1099

5.44

4575

1150

5.79

4866

1201

6.14

5162

1249

6.50

5462

1297

6.86

5766

1343

7.22

6075

8,500

1161

6.22

5232

1210

6.57

5529

1258

6.93

5829

1304

7.29

6134

1349

7.66

6443

1393

8.03

6755

9,000

1223

7.07

5943

1270

7.43

6245

1315

7.79

6550

1360

8.16

6869

1403

8.53

7171

1445

8.90

7487

9,500

1286

7.98

6708

1331

8.34

7014

1374

8.71

7324

1416

9.08

7638

1457

9.46

7954

1498

9.84

8274

10,000

1349

8.95

7528

1392

9.32

7839

1433

9.70

8154

1473

10.07

8471

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

1.4

 

 

1.6

 

 

1.8

 

 

1.9

 

 

2.0

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

 

5,500

1173

4.44

3732

1227

4.80

4036

1279

5.17

4345

1304

5.35

4502

1329

5.54

4629

 

 

 

6,000

1211

4.95

4165

1263

5.32

4471

1313

5.69

4782

1337

5.87

4939

1361

6.06

5097

 

 

 

6,500

1252

5.53

4646

1302

5.89

4954

1350

6.26

5267

1373

6.56

5425

1396

6.64

5584

 

 

 

7,000

1295

6.16

5176

1343

6.52

5487

1389

6.90

5802

1412

7.09

5961

1434

7.28

6121

 

 

 

7,500

1340

6.85

5756

1386

7.22

6070

1431

7.60

6387

1452

7.79

6547

1474

7.98

6709

 

 

 

8,000

1388

7.60

6388

1431

7.97

6704

1474

8.35

7024

1495

8.54

7186

1516

8.74

7348

 

 

 

8,500

1436

8.41

7071

1478

8.79

7390

1520

9.17

7713

1540

9.37

7876

 

 

 

9,000

1486

9.28

7807

1527

9.67

8130

 

 

 

9,500

1538

10.22

8597

 

 

 

10,000

 

 

 

LEGEND

Bhp — Brake Horsepower

Watts — Input Watts to Motor

*Standard low-medium static drive range is 910 to 1095 rpm. Alternate high-static drive range is 1069 to 1287. Other rpms require a field- supplied drive.

Refer to page 32 for general Fan Performance Data notes.

NOTE: Maximum continuous bhp is 5.90. The maximum continuous watts is 5180. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Table 24 for more information.